10.8.4 CUSTOMER INTERFACES (Terminals X1….X4)
10.8.5 CUSTOMER INPUTS DRY PORT s:
Terminal block X1
Connection of Remote Shut down facilities, Generator Operation, Customers specials
(see UM Section 9 / OPTIONS)
10.8.6 CUSTOMER OUTPUTS DRY PORTs : Terminal blocks X2, X3, X4
Provision of signals for the automatic and orderly shutdown of servers, AS400 or Automation building systems
All voltage free contacts are rated 60 VAC max. and 500 mA max.:
All the interfaces are connected to Phoenix Spring terminals with wires : 0.5 mm2
Block Terminal Contact
Signal On
Display
Function
X1
X1 / 1
IN
+ 3.3 Vdc
Remote Shut down
X1 / 2
GND
GND
(Do not remove the factory mounted bridge until external Remote Shut down is connected)
X1 / 3
IN
+ 3.3 Vdc
Generator Operation
X1 / 4
GND
GND
(NC = Generator ON)
X1 / 5
IN
+ 3.3 Vdc
Customer IN 1
X1 / 6
GND
GND
(Function on request, to be defined)
X1 / 7
IN
+ 3.3 Vdc
Customer IN 2
X1 / 8
GND
GND
(Function on request, to be defined)
X1 / 9
IN
+ 3.3 Vdc
Temperature Battery
X1 / 10
GND
GND
(If connected , the battery charger current if depending of the battery temp.)
X2
X2 / 1
NO
MAINS_OK
Mains Present
X2 / 2
NC
ALARM
Mains Failure
X2 / 3
C
Common
X2 / 4
NO
LOAD_ON_INV
Load on Inverter
X2 / 5
NC
Message
(Load on Mains bypass)
X2 / 6
C
Common
X2 / 7
NO
BATT_LOW
Battery Low
X2 / 8
NC
ALARM
Battery OK
X2 / 9
C
Common
X2 / 10
NO
LOAD_ON_MAINS
Load on bypass
(Mains)
X3
X3 / 1
NC
Message
(Load on Inverter)
X3 / 2
C
Common
X3 / 3
NO
COMMON_ALARM
Common Alarm
(System)
X3 / 4
NC
ALARM
NO Alarm Condition
X3 / 5
C
Common
X3 / 6
NO
MODUL_ALARM1
Module 1 Alarm
X3 / 7
NC
ALARM
NO Alarm Condition
X3 / 8
C
Common
X3 / 9
NO
MODUL_ALARM2
Module 2 Alarm
X3 / 10
NC
ALARM
NO Alarm Condition
X4
X4 / 1
C
Common
X4 / 2
NO
MODUL_ALARM3
Module 3 Alarm
X4 / 3
NC
ALARM
NO Alarm Condition
X4 / 4
C
Common
X4 / 5
NO
MODUL_ALARM4
Module 4 Alarm
X4 / 6
NC
ALARM
NO Alarm Condition
X4 / 7
C
Common
X4 / 8
NO
MODUL_ALARM5
Module 5 Alarm
X4 / 9
NC
ALARM
NO Alarm Condition
X4 / 10
C
Common
Phoenix Spring Terminals (X1…X4) Connection