Section-2
04-3008_S2_ABB_OPMCPDPA-S2_GB_121202
Page 14/16 ABB
Printed in Switzerland – Modifications reserved
NOTE
:
For UPS-Modules DPA 30kVA, 40kVA and 50kVA use only 40-50 (only even numbers) of 12V-battery blocks.
NOTE
: Set-up the correct number of battery blocks on Control Panel (Menu: Service-Set-Up)
Frame: Upgrade DPA 250 with Modules DPA 30 S2 or DPA 50 S2
CBAT
DPA-120
CBAT DPA-200
(3x40)x28Ah
(5x40)x28Ah
Dimensions (WxHxD)
mm
730x1975x800
1200x1975x800
Weight with trays and w/o
batteries
kg
290
410
For detailed information and layout of the battery cabinets please refer to section 10
Examples:
On drawing CBAT DPA-120 (3x40)x28Ah battery blocks are fitted. The “A” column of 40x28Ah belongs to
UPS-1, the “B” column of 40x28Ah belongs to UPS-2 and the “C” column of 40x28Ah belongs to UPS-3.
On drawing CBAT DPA-200 (5x40)x28Ah battery blocks are fitted in the battery cabinet and each UPS-Module
is provided with 40x28Ah.
Depending on the request the batteries may be connected separately for each Module or it is possible to
parallel them together into one common battery for five UPS-modules.
CBAT DPA-120
CBAT DPA-200
5x28Ah
1
2
3
4
5
6
7
F3
F1
5x28Ah
5x28Ah
5x28Ah
8
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
F2
A
B
C
Battery Cabinet 120