WYE
5.2.10.
WYE represent DMCD M_ME_NA_1, M_ME_TA_1, M_ME_TD_1, M_ME_NB_1,
M_ME_TB_1, M_ME_NC_1, M_ME_TC_1, M_ME_TF_1.
OPC data types
Protocol informa-
tion element
Mandat-
ory/Optional
Value/ Value
range
Type
Name
VT_R4
VT_I4
VT_DATE
SVA, NVA
OV, BL, SB, NT, IV
CP24Time2A
M
M
M
AnalogueValue
Quality
TimeStamp
phsA.cVal.mag
phsA.q
phsA.t
VT_R4
VT_I4
VT_DATE
SVA, NVA
OV, BL, SB, NT, IV
CP24Time2A
O
O
O
AnalogueValue
Quality
TimeStamp
phsB.cVal.mag
phsB.q
phsB.t
VT_R4
VT_I4
VT_DATE
SVA, NVA
OV, BL, SB, NT, IV
CP24Time2A
O
O
O
AnalogueValue
Quality
TimeStamp
phsC.cVal.mag
phsC.q
phsC.t
VT_R4
VT_I4
VT_DATE
SVA, NVA
OV, BL, SB, NT, IV
CP24Time2A
O
O
O
AnalogueValue
Quality
TimeStamp
neut.cVal.mag
neut.q
neut.t
Delta (DEL)
5.2.11.
DEL represents DMCD M_ME_NA_1, M_ME_TA_1, M_ME_TD_1, M_ME_NB_1,
M_ME_TB_1, M_ME_NC_1, M_ME_TC_1, M_ME_TF_1.
OPC data types
Protocol informa-
tion element
Mandat-
ory/Optional
Value/ Value
range
Type
Name
VT_R4
VT_I4
VT_DATE
SVA, NVA
OV, BL, SB, NT, IV
CP24Time2A
M
M
M
AnalogueValue
Quality
TimeStamp
phsAB. cVal.mag t
phsAB.q
phsAB.t
VT_R4
VT_I4
VT_DATE
SVA, NVA
OV, BL, SB, NT, IV
CP24Time2A
M
M
M
AnalogueValue
Quality
TimeStamp
phsBC.cVal.mag q
phsBC.q
phsBC.t
VT_R4
VT_I4
VT_DATE
SVA, NVA
OV, BL, SB, NT, IV
CP24Time2A
M
M
M
AnalogueValue
Quality
TimeStamp
phsCA.cVal.mag q
phsCA.q
phsCA.t