Description
Value or Value range/ Default
Property / Para-
meter
Specifies whether the handshaking mes-
sages (request, status of link, reset of
remote link) are restarted when a ‘request
status of link’ message is received from
the remote end.
Handshaking messages not
restarted
Handshaking messages
restarted
Default: Handshaking mes-
sages not restarted
Operating Mode
The time that IEC link waits for the end of
the received message in seconds.
0...255
Default: 2
Response Timeout
The number of characters for calculating
delay for resetting RTS signal.
0...20
Default: 1
RTS Keepup Delay
The number of padding characters inser-
ted to the end of telegram to delay the
resetting of RTS signal.
0...255
Default: 0
RTS Keepup Pad-
ding Characters
Delay in milliseconds between receiving
CTS signal and start of transmission.
0...65535
Default: 15
Transmission Wait
Delay
Configuring IEC101 Unbalanced Channel properties
3.4.3.2.
The IEC101 Unbalanced Channel properties that can be configured and value ranges for
them can be found in Table 3.4.3.2-1. The actual configuration by using the COM600
Station Automation Builder 600 (SAB600) is performed as described in 3.4.1, General
about configuring objects.
Table 3.4.3.2-1 IEC101 Unbalanced Channel properties
Description
Value or Value range/ Default
Property / Para-
meter
Basic
Specifies whether channel is initially in
use.
In use
Not in use
Default: In use
In Use
Protocol
IEC60870-5-101 Unbalanced
Slave
Protocol
Communication
Port
24