Protection activation information (ACT)
3.4.5.5.
Table 3.4.5.5-1 Configurable ACT properties for OPC client
Description
Value or Value range/ Default
Property/ Para-
meter
Basic
Common data class according to IEC
61850.
ACT
Common Data
Class
Addresses
IEC address for general indication.
0...16777215
General Address
IEC address for neutral indication
0...16777215
Neutral Address
IEC address for phase A.
0...16777215
0 = Not in use
Phase A Address
IEC address for phase B.
0...16777215
0 = Not in use
Phase B Address
IEC address for phase C.
0...16777215
0 = Not in use
Phase C Address
Common
Class of ASDU. Data sent from the slave
to the master can be assigned to two
classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
class 2.
1 = Class 1
2 = Class 2
Default: 1 = Class 1
Class
Interrogation group. 1 - 16 general or 1 -
4 counter interrogation.
1...16 (general) or 1...4 (coun-
ters)
Interrogation Group
Defines whether a new indication value
overwrites an older one in the queue.
True = 1
False =0
Default: False = 0
Over Write
Priority of ASDU. This property defines
how the ASDU sent is placed in the class
1 and class 2 queues.
0...3
End of queue = 0
Middle = 1, 2
Beginning of queue = 3
Priority
Maximum update rate of indication
changes between OPC server and client
in milliseconds. 0 means that server sends
all the changes to the client.
0...60000
Default: 0
Update Rate
Data Class Spe-
cific
36
1MRS755382
Station Automation COM600 3.4
IEC 60870-5-101 Slave (OPC) User's Manual