![ABB COM600 3.4 User Manual Download Page 22](http://html.mh-extra.com/html/abb/com600-3-4/com600-3-4_user-manual_1209022.webp)
Table 3.4.3.1-1 IEC101 Balanced Channel properties
Description
Value or Value range/ Default
Property / Para-
meter
Basic
Specifies whether the channel is initially
in use or not.
In use
Not in use
Dafault: In use
In Use
Protocol
IEC60870-5-101 Balanced
Slave
Protocol
Communication
Port
Transmission rate used on the channel.
300 bits/s
600 bits/s
1200 bits/s
2400 bits/s
4800 bits/s
9600 bits/s
19200 bits/s
38400 bits/s
56000 bits/s
57600 bits/s
115200 bits/s
128000 bits/s
256000 bits/s
Default: 19200 bits/s
Baud Rate
Serial port used by the IEC60870-5-101
protocol.
Number of ports depends on the used
hardware.
COM1...COM8
Default: COM1
Communication Port
Specifies the parity check used for the
characters transferred on the channel.
No parity check
Even
Odd
Default: Even
Parity
22
1MRS755382
Station Automation COM600 3.4
IEC 60870-5-101 Slave (OPC) User's Manual
Summary of Contents for COM600 3.4
Page 1: ...Station Automation COM600 3 4 IEC 60870 5 101 Slave OPC User s Manual ...
Page 2: ......
Page 6: ...6 ...
Page 76: ...76 ...
Page 81: ......