Description
Value/Value range
Name
The link address of the IEC
60870-5-101 slave station
0...255 or
0...65535
Default: 1
The maximum value depends
on the corresponding Polling
Address Length property value
as follows:
when Polling Address Length
property value is 1, the value
range for the Polling Address
is 0...255 and
when Polling Address Length
property value is 2, the value
range for the Polling Address
is 0...65535
Polling Address
The station address of the IEC
60870-5-101 slave station (the
common address of ASDU in
an IEC message)
0...255 or
0...65535
Default: 1
The maximum value depends
on the corresponding Station
Address Length property value
as follows:
when Station Address Length
property value is 1, the value
range for the Information
Address is 0...255 and
when Station Address Length
property value is 2, the value
range for the Station Address
is 0...65535
Station Address
Communication control
Defines how many data items
can be written without a reply
or request from the master.
0...100
Default: 10
Reply Window Size
Enables or disables single char
responses.
Disabled
Enabled
Default: Disabled
Single Char Response
Command Handling
28
1MRS755382
Station Automation COM600 3.4
IEC 60870-5-101 Slave (OPC) User's Manual