Table 3.4.2-1 IEC101 Slave OPC Client properties
Description
Value or Value range/ Default
Property / Para-
meter
Basic
Specifies the maximum time in seconds
that any connected (configured) OPC
Server requires to retrieve all its initial
data.
0...65535
Default: 5
Maximum OPC
Server Initialization
Time
Instance identification of diagnostic OPC
alarm and event server.
Prog ID AE
Instance identification of diagnostic OPC
data access server.
ProgID DA
The value of this property in minutes is
added to the synchronization time received
from an IEC101 master.
-720...720
Default: 0
Time Zone Correc-
tion
Station/Remote
Switch
Specifies if a position check for the station
remote switch is going to be made.
Do not check Station/Remote
switch position, command
always allowed.
Check Station/Remote switch
position.
Default: Do not check Sta-
tion/Remote switch position,
command always allowed.
Station/Remote
Switch
Specifies what to do with commands if the
position of the switch is uncertain.
Reject commands if position
bad or unknown.
Allow commands if position bad
or unknown.
Default: Reject commands if
position bad or unknown
Station/Remote
Switch Error
Configuring Channel Properties
3.4.3.
Configuring IEC101 Balanced Channel properties
3.4.3.1.
The IEC101 Balanced Channel properties that can be configured and value ranges for
them can be found in Table 3.4.3.1-1. The actual configuration by using the COM600
Station Automation Builder 600 (SAB600) is performed as described in 3.4.1, General
about configuring objects.
21
Station Automation COM600 3.4
1MRS755382
IEC 60870-5-101 Slave (OPC) User's Manual