70 Electrical installation
Connecting the generator cables
Connection diagram
Connection procedure
WARNING!
See and obey the safety instructions of the converter. If you ignore
them, injury or death, or damage to the equipment can occur.
WARNING!
Apply grease to stripped aluminum conductors before attaching them
to non-coated aluminum cable lugs. Obey the grease manufacturer’s instructions.
Aluminum-aluminum contact can cause oxidation in the contact surfaces.
1. Open the door of the generator cable connection cubicle (see figures on the next
page).
2. Remove the shroud that protects the generator cable connection busbars and cable
entries.
3. Ensure that foreign objects (screws, etc.) cannot fall inside the converter module.
During installation, cover the top of the module with plastic, fabric etc.
WARNING!
Foreign objects inside the converter module can cause eg, short-
circuit. Injury or death, or damage to the equipment can occur.
4. When shielded cable is used:
•
Lead the cables into the inside of the cubicle. Ground a shielded cable 360° at the
lead-through with an EMC cable gland (to be supplied by the customer).
•
Connect the cables as follows:
•
Cut the cables to suitable length. Strip the cables and conductors. Fasten the
cable lugs to the conductor ends.
•
Twist the cable shields into bundles and connect to the cabinet PE (ground)
busbar. Connect any separate ground conductors or cables to the cabinet PE
(ground) busbar.
•
Connect the phase conductors to terminals U2, V2 and W2. See the appropriate
connection diagram above. Tighten the phase conductors and PE to a 120 N·m
(89 lbf·ft) torque.
PE
G
3~
W1
U1
V1
PE
W2
V2
U2
Summary of Contents for ACS880-87LC-4000A/4021A-7
Page 4: ......
Page 10: ...10 ...
Page 17: ...Safety instructions 17 1 3 2 4 5 6 7 ...
Page 18: ...18 Safety instructions 8 9 ...
Page 28: ...28 Introduction to the manual ...
Page 52: ...52 Mechanical installation ...
Page 66: ...66 Planning the electrical installation ...
Page 74: ...74 Electrical installation Diagrams for the customer connections are presented below ...
Page 75: ...Electrical installation 75 optional Fast shutdown ...
Page 85: ...Maintenance 85 b c a Air flow direction 2 3 4 6 ...
Page 87: ...Maintenance 87 2 5 4 ...
Page 88: ...88 Maintenance 7 Arrow indicating the air flow direction 5 6 6 ...
Page 90: ...90 Maintenance Air flow circulation b a ...
Page 106: ...106 Maintenance ...
Page 124: ...124 Control units of the converter ...
Page 126: ...126 Dimension drawings ...
Page 127: ...Dimension drawings 127 ...
Page 128: ...128 Dimension drawings ...
Page 142: ...142 Cooling and heating ...