Mechanical installation 49
Placing the converter
The cabinet can be placed into its final position with an iron bar and a wooden piece at the
bottom edge of the cabinet. Place the wooden piece carefully to avoid damage to the
cabinet frame.
The cabinet has a back-to-back design, and thus you cannot install it with a longer side
against a wall.
The converter must be installed in an upright vertical position.
Notes:
•
Leave a 400 mm (16 in) clearance above the converter cabinet to allow pressure
release lids to open in an arc fault situation.
•
Leave space at the side for the coolant pipes.
•
You can adjust the height, for example, if the floor is uneven by using metal shims
between the cabinet frame and floor.
> 400 mm (16 in)
Summary of Contents for ACS880-87LC-4000A/4021A-7
Page 4: ......
Page 10: ...10 ...
Page 17: ...Safety instructions 17 1 3 2 4 5 6 7 ...
Page 18: ...18 Safety instructions 8 9 ...
Page 28: ...28 Introduction to the manual ...
Page 52: ...52 Mechanical installation ...
Page 66: ...66 Planning the electrical installation ...
Page 74: ...74 Electrical installation Diagrams for the customer connections are presented below ...
Page 75: ...Electrical installation 75 optional Fast shutdown ...
Page 85: ...Maintenance 85 b c a Air flow direction 2 3 4 6 ...
Page 87: ...Maintenance 87 2 5 4 ...
Page 88: ...88 Maintenance 7 Arrow indicating the air flow direction 5 6 6 ...
Page 90: ...90 Maintenance Air flow circulation b a ...
Page 106: ...106 Maintenance ...
Page 124: ...124 Control units of the converter ...
Page 126: ...126 Dimension drawings ...
Page 127: ...Dimension drawings 127 ...
Page 128: ...128 Dimension drawings ...
Page 142: ...142 Cooling and heating ...