86 Maintenance
Replacing the fan of the main breaker cubicle
WARNING!
Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the converter. If you ignore the instructions,
physical injury, death, or damage to the equipment can occur.
1. Disconnect the converter from the all power sources and make sure it is safe to start
the work. See the safety instructions.
2. Detach the shroud in front of the fan of the main breaker cubicle.
3. Pull the shroud carefully out of the cabinet. Observe the cable rail on top of the main
circuit breaker when removing the shroud.
4. Disconnect the wiring plug of the fan.
5. Remove the fastening screws of the plate in front of the fans and remove the plate.
6. Remove the fastening screws of the fan support plate and pull the support plate and
the fan out.
7. Remove the fastening screws of the fan grille (M5×10, 4 pcs) and detach the fan grille.
8. Remove the fastening screws of the fan (M4, 4 pcs).
9. Replace the fan.
10. Install a new fan in reverse order. Check that the air flow direction is correct (an arrow
indicating the direction is marked on the side of the fan).
Summary of Contents for ACS880-87LC-4000A/4021A-7
Page 4: ......
Page 10: ...10 ...
Page 17: ...Safety instructions 17 1 3 2 4 5 6 7 ...
Page 18: ...18 Safety instructions 8 9 ...
Page 28: ...28 Introduction to the manual ...
Page 52: ...52 Mechanical installation ...
Page 66: ...66 Planning the electrical installation ...
Page 74: ...74 Electrical installation Diagrams for the customer connections are presented below ...
Page 75: ...Electrical installation 75 optional Fast shutdown ...
Page 85: ...Maintenance 85 b c a Air flow direction 2 3 4 6 ...
Page 87: ...Maintenance 87 2 5 4 ...
Page 88: ...88 Maintenance 7 Arrow indicating the air flow direction 5 6 6 ...
Page 90: ...90 Maintenance Air flow circulation b a ...
Page 106: ...106 Maintenance ...
Page 124: ...124 Control units of the converter ...
Page 126: ...126 Dimension drawings ...
Page 127: ...Dimension drawings 127 ...
Page 128: ...128 Dimension drawings ...
Page 142: ...142 Cooling and heating ...