68 Electrical installation
Grid cable
Check the insulation of the grid cable according to local regulations before connecting it to
the converter.
Generator stator and generator cable
Check the insulation of the generator stator and cable as follows:
•
Check that all cables are disconnected from the converter output terminals U2, V2 and
W2.
•
Measure the insulation resistance between each phase conductor and the protective
ground conductor using a measuring voltage of 1000 V DC. The insulation resistance
of an ABB generator must exceed 100 Mohm (reference value at 25 °C or 77 °F). For
the insulation resistance of other generators, please consult the manufacturer’s
instructions.
•
Note:
Make sure that there is no condensed moisture inside the generator casing. If
you suspect that there is moisture, dry the generator before measurement.
•
Note:
When using permanent magnet generator, it must be stable at the time of the
measurement.
Integrated DC chopper and DC resistor (D150+D151)
Every converter equipped with integrated DC chopper and DC resistor is tested for
insulation between the main circuit and the chassis at the factory (2700 V rms 50 Hz for
1 second). Do not make any voltage tolerance or insulation resistance tests.
Connecting the grid cables/busbars
Connection diagram
ohm
G
3~
U1
V1
W1 PE
U<
PE
L1
L2
L3
PE
Summary of Contents for ACS880-87LC-4000A/4021A-7
Page 4: ......
Page 10: ...10 ...
Page 17: ...Safety instructions 17 1 3 2 4 5 6 7 ...
Page 18: ...18 Safety instructions 8 9 ...
Page 28: ...28 Introduction to the manual ...
Page 52: ...52 Mechanical installation ...
Page 66: ...66 Planning the electrical installation ...
Page 74: ...74 Electrical installation Diagrams for the customer connections are presented below ...
Page 75: ...Electrical installation 75 optional Fast shutdown ...
Page 85: ...Maintenance 85 b c a Air flow direction 2 3 4 6 ...
Page 87: ...Maintenance 87 2 5 4 ...
Page 88: ...88 Maintenance 7 Arrow indicating the air flow direction 5 6 6 ...
Page 90: ...90 Maintenance Air flow circulation b a ...
Page 106: ...106 Maintenance ...
Page 124: ...124 Control units of the converter ...
Page 126: ...126 Dimension drawings ...
Page 127: ...Dimension drawings 127 ...
Page 128: ...128 Dimension drawings ...
Page 142: ...142 Cooling and heating ...