Wiring
For the electrical specifications of the STO connection, see the technical data of the control
unit.
■
Activation switch
In the wiring diagrams, the activation switch has the designation [K]. This represents a
component such as a manually operated switch, an emergency stop push button switch, or
the contacts of a safety relay or safety PLC.
• In case a manually operated activation switch is used, the switch must be of a type that
can be locked out to the open position.
• The contacts of the switch or relay must open/close within 200 ms of each other.
• An FSO-xx safety functions module or an FPTC-0x thermistor protection module can
also be used. For more information, see the module documentation.
■
Cable types and lengths
• Double-shielded twisted-pair cable is recommended.
• Maximum cable lengths:
• 300 m (1000 ft) between activation switch [K] and drive control unit
• 60 m (200 ft) between multiple drives
• 60 m (200 ft) between external power supply and first control unit
• 30 m (100 ft) between BCU control unit and last inverter module in the chain.
Note:
A short-circuit in the wiring between the switch and an STO terminal causes a
dangerous fault. Therefore, it is recommended to use a safety relay (including wiring
diagnostics) or a wiring method (shield grounding, channel separation) which reduces or
eliminates the risk caused by the short-circuit.
Note:
The voltage at the STO input terminals of the control unit (or frame R8i inverter module)
must be at least 17 V DC to be interpreted as “1”.
The pulse tolerance of the input channels is 1 ms.
■
Grounding of protective shields
• Ground the shield in the cabling between the activation switch and the control unit at the
control unit only.
• Ground the shield in the cabling between two control units at one control unit only.
• Do not ground the shield in the cabling between BCU and R8i module, or between R8i
modules.
The Safe torque off function 85
Summary of Contents for ACS880-107LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 107LC inverter units Hardware manual ...
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 38: ...4 a 8 b 16 18 PE PE 10 38 Electrical installation ...
Page 39: ...13 12 21 Electrical installation 39 11 ...
Page 44: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 44 Electrical installation ...
Page 48: ...48 ...
Page 54: ...54 ...
Page 72: ...72 ...
Page 108: ...108 ...
Page 115: ...Above Sides Front in mm in mm in mm 9 85 250 0 0 59 1500 Technical data 115 ...
Page 124: ...124 ...
Page 130: ...Inverter module cubicle with two R8i modules bottom cable exit 130 Dimensions ...
Page 131: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 131 ...
Page 133: ...Cubicle width 300 mm top cable exit Dimensions 133 ...
Page 134: ...Cubicle width 400 mm bottom cable exit 134 Dimensions ...
Page 135: ...Cubicle width 400 mm top cable exit Dimensions 135 ...
Page 136: ...Cubicle width 600 mm bottom cable exit 136 Dimensions ...
Page 137: ...Cubicle width 600 mm top cable exit Dimensions 137 ...
Page 138: ...138 ...