Make sure that …
There is an adequately sized protective earth (ground) conductor(s) between the drive and the
switchboard, the conductor is connected to correct terminal, and the terminal is tightened to the correct
torque.
Proper grounding has also been measured according to the regulations.
If the drive is equipped with a DC/DC converter unit: There is an adequately sized protective earth
(ground) conductor between the energy storage and the DC/DC converter, the conductor has been
connected to appropriate terminal, and the terminal has been tightened to the proper torque. Proper
grounding has also been measured according to the regulations.
If the drive is equipped with a DC/DC converter unit: The energy storage cable has been connected to
the correct terminals of the DC/DC converter and energy storage, and the terminals have been tightened
to the proper torque.
If the drive is equipped with a DC/DC converter unit: The energy storage has been equipped with fuses
for protecting energy storage cable in a cable short-circuit situation.
If the drive is equipped with a DC/DC converter unit: The energy storage has been equipped with a
disconnecting device.
The input power cable is connected to the correct terminals, the phase order is correct, and the terminals
are tightened to the correct torque.
There is an adequately sized protective earth (ground) conductor between the motor and the drive,
and the conductor is connected to the correct terminal, and the terminal is tightened to the correct
torque.
Proper grounding has also been measured according to the regulations.
The motor cable is connected to the correct terminals, the phase order is correct, and the terminals
are tightened to the correct torque.
The motor cable is routed away from other cables.
No power factor compensation capacitors are connected to the motor cable.
If an external brake resistor is connected to the drive: There is an adequately sized protective earth
(ground) conductor between the brake resistor and the drive, and the conductor is connected to the
correct terminal, and the terminals are tightened to the correct torque. Proper grounding has also been
measured according to the regulations.
If an external brake resistor is connected to the drive: The brake resistor cable is connected to the
correct terminals, and the terminals are tightened to the correct torque.
If an external brake resistor is connected to the drive: The brake resistor cable is routed away from
other cables.
The control cables are connected to the correct terminals, and the terminals are tightened to the correct
torque.
The voltage setting of the auxiliary voltage transformers (if any) is correct. See the electrical installation
instructions.
If a drive bypass connection will be used: The direct-on-line contactor of the motor and the drive output
contactor are either mechanically and/or electrically interlocked, that is, they cannot be closed at the
same time. A thermal overload device must be used for protection when bypassing the drive. Refer to
local codes and regulations.
There are no tools, foreign objects or dust from drilling inside the drive.
Cover(s) of the motor connection box are in place. Cabinet shrouds are in place and doors are closed.
The motor and the driven equipment are ready for power-up.
The coolant connections between cubicles (if any) and to the cooling circuit are tight.
If the drive is equipped with a cooling unit: Refer to the cooling unit documentation for specific tasks.
50 Installation checklist
Summary of Contents for ACS880-107LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 107LC inverter units Hardware manual ...
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 38: ...4 a 8 b 16 18 PE PE 10 38 Electrical installation ...
Page 39: ...13 12 21 Electrical installation 39 11 ...
Page 44: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 44 Electrical installation ...
Page 48: ...48 ...
Page 54: ...54 ...
Page 72: ...72 ...
Page 108: ...108 ...
Page 115: ...Above Sides Front in mm in mm in mm 9 85 250 0 0 59 1500 Technical data 115 ...
Page 124: ...124 ...
Page 130: ...Inverter module cubicle with two R8i modules bottom cable exit 130 Dimensions ...
Page 131: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 131 ...
Page 133: ...Cubicle width 300 mm top cable exit Dimensions 133 ...
Page 134: ...Cubicle width 400 mm bottom cable exit 134 Dimensions ...
Page 135: ...Cubicle width 400 mm top cable exit Dimensions 135 ...
Page 136: ...Cubicle width 600 mm bottom cable exit 136 Dimensions ...
Page 137: ...Cubicle width 600 mm top cable exit Dimensions 137 ...
Page 138: ...138 ...