Installing option modules
■
Mechanical installation of I/O extension, fieldbus adapter and pulse
encoder interface modules
See hardware description for the available slots for each module. Install the option modules
as follows:
WARNING!
Obey the safety instructions given in
ACS880 liquid-cooled multidrive
cabinets and modules safety instructions
(3AXD50000048633 [English]).
If you ignore the safety instructions, injury or death, or damage to the
equipment can occur.
If you are not a qualified electrical professional, do not do installation or
maintenance work.
1. Stop the drive and do the steps in section
Electrical safety precautions (page 27)
before
you start the work.
2. Open the door of the auxiliary control cubicle (ACU).
3. Remove the shrouding at the top of the cubicle.
4. Locate the inverter control unit (A41).
5. Insert the module carefully into its position on the control unit.
6. Fasten the mounting screw.
Note:
The screw secures and grounds the module. It is essential for fulfilling the EMC
requirements and for proper operation of the module.
■
Installation of an FSO-xx safety functions module onto BCU
WARNING!
Read the safety instructions given in
Safety instructions for ACS880
liquid-cooled multidrive cabinets and modules
(3AXD50000048633
[English]). If you ignore them, injury or death, or damage to the equipment
can occur.
This procedure describes the installation of an FSO-xx safety functions module onto the
BCU control unit. (The FSO-xx can alternatively be installed beside the control unit, which
is the standard with factory-installed FSO-xx modules. For instructions, see the FSO-xx
manual.)
1. Stop the drive and do the steps in section
Electrical safety precautions (page 27)
before
you start the work.
2. The FSO-xx comes with alternative bottom plates for mounting on different units. For
mounting on the BCU, the mounting points should be located at the long edges of the
module as shown. Replace the bottom plate of the FSO-xx if necessary.
Electrical installation 45
11
Summary of Contents for ACS880-107LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 107LC inverter units Hardware manual ...
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 38: ...4 a 8 b 16 18 PE PE 10 38 Electrical installation ...
Page 39: ...13 12 21 Electrical installation 39 11 ...
Page 44: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 44 Electrical installation ...
Page 48: ...48 ...
Page 54: ...54 ...
Page 72: ...72 ...
Page 108: ...108 ...
Page 115: ...Above Sides Front in mm in mm in mm 9 85 250 0 0 59 1500 Technical data 115 ...
Page 124: ...124 ...
Page 130: ...Inverter module cubicle with two R8i modules bottom cable exit 130 Dimensions ...
Page 131: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 131 ...
Page 133: ...Cubicle width 300 mm top cable exit Dimensions 133 ...
Page 134: ...Cubicle width 400 mm bottom cable exit 134 Dimensions ...
Page 135: ...Cubicle width 400 mm top cable exit Dimensions 135 ...
Page 136: ...Cubicle width 600 mm bottom cable exit 136 Dimensions ...
Page 137: ...Cubicle width 600 mm top cable exit Dimensions 137 ...
Page 138: ...138 ...