• Cut the shield at the midpoint of the bare part. Be careful not to cut the conductors or
the grounding wire (if present).
• Turn the shield inside out to expose its conductive surface.
• Cover the turned shield and the stripped cable with copper foil to keep the shielding
continuous.
1
A
B
C
2
2
3
4
5
Stripped cable
A
Conductive surface of the shield exposed
B
Stripped part covered with copper foil
C
Cable shield
1
Copper foil
2
Shielded twisted pair
3
Grounding wire
4
Note for top entry of cables:
When each cable has its own rubber grommet, sufficient IP
and EMC protection can be achieved. However, if there is more than one cable per grommet,
plan the installation beforehand as follows:
1. Make a list of the cables coming to the cabinet.
2. Sort the cables going to the left into one group and the cables going to the right into
another group to avoid unnecessary crossing of cables inside the cabinet.
3. Sort the cables in each group according to size.
4. Group the cables for each grommet as follows ensuring that each cable has a proper
contact to the cushions on both sides.
Max. number of cables per grommet
Cable diameter in mm
4
≤ 13
3
≤ 17
2
< 25
1
≥ 25
32 Electrical installation
Summary of Contents for ACS880-107LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 107LC inverter units Hardware manual ...
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 38: ...4 a 8 b 16 18 PE PE 10 38 Electrical installation ...
Page 39: ...13 12 21 Electrical installation 39 11 ...
Page 44: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 44 Electrical installation ...
Page 48: ...48 ...
Page 54: ...54 ...
Page 72: ...72 ...
Page 108: ...108 ...
Page 115: ...Above Sides Front in mm in mm in mm 9 85 250 0 0 59 1500 Technical data 115 ...
Page 124: ...124 ...
Page 130: ...Inverter module cubicle with two R8i modules bottom cable exit 130 Dimensions ...
Page 131: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 131 ...
Page 133: ...Cubicle width 300 mm top cable exit Dimensions 133 ...
Page 134: ...Cubicle width 400 mm bottom cable exit 134 Dimensions ...
Page 135: ...Cubicle width 400 mm top cable exit Dimensions 135 ...
Page 136: ...Cubicle width 600 mm bottom cable exit 136 Dimensions ...
Page 137: ...Cubicle width 600 mm top cable exit Dimensions 137 ...
Page 138: ...138 ...