The Safe torque off function
Contents of this chapter
This chapter describes the Safe torque off (STO) function of the drive and gives instructions
for its use.
Note:
In this chapter, the term 'drive' refers to one inverter unit of the drive system.
Description
WARNING!
In case of parallel-connected drives or dual-winding motors, the STO must be
activated on each drive to remove the torque from the motor.
The Safe torque off function can be used, for example, as the final actuator device of safety
circuits that stop the drive in case of danger (such as an emergency stop circuit). Another
typical application is a prevention of unexpected start-up function that enables short-time
maintenance operations like cleaning or work on non-electrical parts of the machinery without
switching off the power supply to the drive.
When activated, the Safe torque off function disables the control voltage for the power
semiconductors of the drive output stage (A, see the diagrams below), thus preventing the
drive from generating the torque required to rotate the motor. If the motor is running when
Safe torque off is activated, it coasts to a stop.
The Safe torque off function has a redundant architecture, that is, both channels must be
used in the safety function implementation. The safety data given in this manual is calculated
for redundant use, and does not apply if both channels are not used.
8
The Safe torque off function 83
Summary of Contents for ACS880-107LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 107LC inverter units Hardware manual ...
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 38: ...4 a 8 b 16 18 PE PE 10 38 Electrical installation ...
Page 39: ...13 12 21 Electrical installation 39 11 ...
Page 44: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 44 Electrical installation ...
Page 48: ...48 ...
Page 54: ...54 ...
Page 72: ...72 ...
Page 108: ...108 ...
Page 115: ...Above Sides Front in mm in mm in mm 9 85 250 0 0 59 1500 Technical data 115 ...
Page 124: ...124 ...
Page 130: ...Inverter module cubicle with two R8i modules bottom cable exit 130 Dimensions ...
Page 131: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 131 ...
Page 133: ...Cubicle width 300 mm top cable exit Dimensions 133 ...
Page 134: ...Cubicle width 400 mm bottom cable exit 134 Dimensions ...
Page 135: ...Cubicle width 400 mm top cable exit Dimensions 135 ...
Page 136: ...Cubicle width 600 mm bottom cable exit 136 Dimensions ...
Page 137: ...Cubicle width 600 mm top cable exit Dimensions 137 ...
Page 138: ...138 ...