Default I/O diagram of the inverter control unit (A41)
The diagram below shows the default I/O connections on the inverter control unit (A41),
and describes the use of the connections in the inverter unit. Under normal circumstances,
the factory-made wiring should not be changed.
The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5 …
2.5 mm
2
(24…12 AWG). The torque is 0.5 N·m (5 lbf·in).
Drive-to-drive link
XD2D
Drive-to-drive link
1)
B
1
A
2
BGND
3
Shield
4
RS485 connection
X485
Not in use
B
5
A
6
BGND
7
Shield
8
Relay outputs
XRO1…XRO3
Ready
250 V AC / 30 V DC
2 A
NC
11
COM
12
NO
13
Running
250 V AC / 30 V DC
2 A
NC
21
COM
22
NO
23
Faulted(-1)
250 V AC / 30 V DC
2 A
NC
31
COM
32
NO
33
Safe torque off
XSTO, XSTO OUT
Safe torque off input. Both circuits must be closed for the
drive to start.
2)
OUT
1
SGND
2
IN1
3
IN2
4
Safe torque off output to inverter modules
2)
IN1
5
SGND
6
IN2
7
SGND
8
Digital inputs
XDI
Stop (0) / Start (1)
DI1
1
Forward (0) / Reverse (1)
DI2
2
Reset
DI3
3
Acceleration & deceleration select
3)
DI4
4
Constant speed 1 select (1 = on)
4)
DI5
5
By default not in use.
DI6
6
Run enable
5)
DIIL
7
Digital input/outputs
XDIO
Output: Ready
DIO1
1
Output: Running
DIO2
2
Digital input/output ground
DIOGND
3
Digital input/output ground
DIOGND
4
Auxiliary voltage output
XD24
+24 V DC 200 mA
6)
+24VD
5
Digital input ground
DICOM
6
+24 V DC 200 mA
6)
+24VD
7
Digital input/output ground
DIOGND
8
Ground selection switch
7)
DICOM=DIOGND
Analog inputs, reference voltage output
AI
10 V DC,
R
L
1…10 kohm
+VREF
1
-10 V DC,
R
L
1…10 kohm
-VREF
2
Ground
AGND
3
Speed reference
0(2)…10 V,
R
in
> 200 kohm
8)
AI1+
4
AI1-
5
By default not in use.
0(4)…20 mA,
R
in
= 100 ohm
9)
AI2+
6
AI2-
7
Analog outputs
AO
Motor speed rpm
0…20 mA,
R
L
< 500 ohm
AO1
1
AGND
2
Motor current
0…20 mA,
R
L
< 500 ohm
AO2
3
AGND
4
External power input
XPOW
24 V DC, 2.05 A
Two supplies can be connected for redundancy.
+24VI
1
GND
2
+24VI
3
GND
4
Safety functions module connection
X12
Control panel connection
X13
Memory unit connection
X205
Fault
To inverter modules
76 Control units of the drive
Summary of Contents for ACS880-107LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 107LC inverter units Hardware manual ...
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 38: ...4 a 8 b 16 18 PE PE 10 38 Electrical installation ...
Page 39: ...13 12 21 Electrical installation 39 11 ...
Page 44: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 44 Electrical installation ...
Page 48: ...48 ...
Page 54: ...54 ...
Page 72: ...72 ...
Page 108: ...108 ...
Page 115: ...Above Sides Front in mm in mm in mm 9 85 250 0 0 59 1500 Technical data 115 ...
Page 124: ...124 ...
Page 130: ...Inverter module cubicle with two R8i modules bottom cable exit 130 Dimensions ...
Page 131: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 131 ...
Page 133: ...Cubicle width 300 mm top cable exit Dimensions 133 ...
Page 134: ...Cubicle width 400 mm bottom cable exit 134 Dimensions ...
Page 135: ...Cubicle width 400 mm top cable exit Dimensions 135 ...
Page 136: ...Cubicle width 600 mm bottom cable exit 136 Dimensions ...
Page 137: ...Cubicle width 600 mm top cable exit Dimensions 137 ...
Page 138: ...138 ...