Installation
73
Note 6:
Alternative installation means
In addition to the installation examples presented in this chapter, there are a few
alternative installation means, such as:
• The power cables can be connected directly to the drive module input and output
terminals with cable lugs or by busbars. The drive module can also be installed
self standing to the floor in an electrical equipment room when the power cable
terminals and electrical parts are protected against contact and the unit is
grounded properly.
• The drive module without pedestal (0H354) can be mounted on wall or
cabinet with four screws through the fastening holes at the top and bottom of the
right-hand side of the module.
Safety
WARNING!
Only qualified electricians are allowed to carry out the electrical
installation work described in this chapter. Follow the
on the first
pages of this manual. Ignoring the safety instructions can cause injury or death.
Checking the installation site
The material below the drive must be non-flammable and strong enough to carry the
weight of the drive.
for the allowed ambient conditions and
Losses, cooling data and noise
on page
for the required cooling air.
Required tools
• Set of screw drivers (Torx and Pozidrive)
• Torque wrench with a 500 mm (20 in.) or 2 × 250 mm (2 × 10 in.) long extension
bar
• 17 mm (11/16 in.) magnetic-end socket for mounting the drive module busbars to
the optional cabling panels (+H381 or +H383)
• 10 mm magnetic-end socket or a torx screw driver for mounting the drive module
top fastening bracket to the cabinet back and for mounting the optional cabling
panels (+H381 or +H383) to the cabinet side panels
• 13 mm socket for mounting the drive module to the cabinet bottom plate or floor
• 22 mm magnetic-end socket for mounting the cable lugs to the terminals (M12
bolt).
Summary of Contents for ACS850-04 series
Page 1: ...ABB machinery drives Hardware manual ACS850 04 drive modules 160 to 560 kW 200 to 700 hp ...
Page 4: ......
Page 12: ...Table of contents 12 ...
Page 20: ...Safety instructions 20 ...
Page 26: ...Introduction to the manual 26 ...
Page 81: ...Installation 81 Assembly drawing frame G1 3AUA0000132078 ...
Page 82: ...Installation 82 Assembly drawing frame G2 3AUA0000132062 ...
Page 83: ...Installation 83 Assembly drawing air baffles 3AUA0000132062 ...
Page 92: ...Installation 92 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Page 112: ...Installation checklist 112 ...
Page 114: ...Start up 114 ...
Page 116: ...Fault tracing 116 ...
Page 140: ...Technical data 140 ...
Page 142: ...Dimension drawings 142 Frame G1 Drive module dimensions ...
Page 143: ...Dimension drawings 143 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Page 144: ...Dimension drawings 144 ...
Page 145: ...Dimension drawings 145 Frame G1 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Page 146: ...Dimension drawings 146 Frame G2 Drive module dimensions ...
Page 147: ...Dimension drawings 147 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Page 148: ...Dimension drawings 148 ...
Page 149: ...Dimension drawings 149 Frame G2 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Page 150: ...Dimension drawings 150 Frames G1 and G2 Bottom plate 3AUA0000082240 ...
Page 151: ...Dimension drawings 151 Frames G1 and G2 Air baffles 3AUA0000138986 ...
Page 152: ...Dimension drawings 152 ...
Page 162: ...du dt filters 162 ...
Page 164: ...3AUA0000081249 Rev C EN 2013 04 11 Contact us www abb com drives www abb com drivespartners ...