Technical data
127
Fuses (IEC)
Fuses (UL)
Note 1:
See also
Implementing thermal overload and short-circuit protection
on page
Note 2:
In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3:
Larger fuses than the recommended ones must not be used.
Note 4:
Fuses from other manufacturers can be used if they meet the ratings and the melting curve of
the fuse does not exceed the melting curve of the fuse mentioned in the table.
Ultrarapid (aR) fuses
Drive type
ACS850-04
Input
current
A
Fuse
A
A
2
s
V
Manufacturer
Type DIN 43620
Size
-387A-5
380
630
220000
690
Bussmann
170M6810D
DIN3
-500A-5
490
800
490000
690
Bussmann
170M6812D
DIN3
-580A-5
570
1000
985000
690
Bussmann
170M6814D
DIN3
-650A-5
640
1000
985000
690
Bussmann
170M6814D
DIN3
-710A-5
690
1250
2150000
690
Bussmann
170M8554D
DIN3
-807A-5
790
1600
4150000
690
Bussmann
170M8557D
DIN3
-875A-5
860
1600
4150000
690
Bussmann
170M8557D
DIN3
aR fuses with flush end contact
Drive type
ACS850-04
Input
current
A
Fuse
A
A
2
s
V
Manufacturer
Size
-710A-5
690
1400
1400000
690
Bussmann
170M7060 *
)
DIN4
-807A-5
790
1400
1400000
690
Bussmann
170M7060 *
)
DIN4
-875A-5
860
1400
1400000
690
Bussmann
170M7060 *
)
DIN4
3AXD00000581898
*
)
or equivalent Bussmann type: 170M7080, 170M7100, 170M7120
UL recognised Class T / Class L fuses
Drive type
ACS850-04
Input
current
A
Fuse
A
V
Manufacturer
UL Class
Bussmann/
Ferraz type
-387A-5
380
500
600
Bussmann
T
JJS-500
-500A-5
490
600
600
Bussmann
T
JJS-600
-580A-5
570
800
600
Ferraz
L
A4BY800
-650A-5
640
800
600
Ferraz
L
A4BY800
-710A-5
690
800
600
Ferraz
L
A4BY800
-807A-5
790
900
600
Ferraz
L
A4BY900
-875A-5
860
1000
600
Ferraz
L
A4BY1000
3AXD00000581898
Summary of Contents for ACS850-04 series
Page 1: ...ABB machinery drives Hardware manual ACS850 04 drive modules 160 to 560 kW 200 to 700 hp ...
Page 4: ......
Page 12: ...Table of contents 12 ...
Page 20: ...Safety instructions 20 ...
Page 26: ...Introduction to the manual 26 ...
Page 81: ...Installation 81 Assembly drawing frame G1 3AUA0000132078 ...
Page 82: ...Installation 82 Assembly drawing frame G2 3AUA0000132062 ...
Page 83: ...Installation 83 Assembly drawing air baffles 3AUA0000132062 ...
Page 92: ...Installation 92 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Page 112: ...Installation checklist 112 ...
Page 114: ...Start up 114 ...
Page 116: ...Fault tracing 116 ...
Page 140: ...Technical data 140 ...
Page 142: ...Dimension drawings 142 Frame G1 Drive module dimensions ...
Page 143: ...Dimension drawings 143 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Page 144: ...Dimension drawings 144 ...
Page 145: ...Dimension drawings 145 Frame G1 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Page 146: ...Dimension drawings 146 Frame G2 Drive module dimensions ...
Page 147: ...Dimension drawings 147 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Page 148: ...Dimension drawings 148 ...
Page 149: ...Dimension drawings 149 Frame G2 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Page 150: ...Dimension drawings 150 Frames G1 and G2 Bottom plate 3AUA0000082240 ...
Page 151: ...Dimension drawings 151 Frames G1 and G2 Air baffles 3AUA0000138986 ...
Page 152: ...Dimension drawings 152 ...
Page 162: ...du dt filters 162 ...
Page 164: ...3AUA0000081249 Rev C EN 2013 04 11 Contact us www abb com drives www abb com drivespartners ...