Planning the electrical installation
64
Implementing the Emergency stop function
For safety reasons, install the emergency stop devices at each operator control
station and at other operating stations where emergency stop may be needed.
Note:
Pressing the stop key (
) on the control panel of the drive does not generate
an emergency stop of the motor or separate the drive from dangerous potential.
Implementing the Safe torque off function
The drive includes the Safe torque off function. For more information, see
Safe
torque off function for ACSM1, ACS850 and ACQ810 drives application guide
(3AFE68929814 [English]).
Implementing the ATEX-certified Safe motor disconnection function
(Q971)
With Q971, the drive provides ATEX-certified safe motor disconnection
without contactor using the drive Safe torque off function. For more information, see
ATEX-certified Safe disconnection function for ACS850 drives (+Q971) application
guide
(3AUA0000074343 [English]).
Implementing the Power loss ride-through function
Implement the power loss ride-through function as follows:
1. Activate the power loss ride-through function of the drive (parameter
47.02 Undervolt ctrl
in the Standard Control Program).
2. If the installation is equipped with a main contactor, prevent its tripping at the input
power break. For example, use a time delay relay (hold) in the contactor control
circuit.
WARNING!
Make sure that the flying restart of the motor will not cause any danger.
If you are in doubt, do not implement the power-loss ride-through function.
Using power factor compensation capacitors with the drive
Power factor compensation is not needed with AC drives. However, if a drive is to be
connected in a system with compensation capacitors installed, note the following
restrictions.
WARNING!
Do not connect power factor compensation capacitors or harmonic
filters to the motor cables (between the drive and the motor). They are not meant to
be used with AC drives and can cause permanent damage to the drive or
themselves.
Summary of Contents for ACS850-04 series
Page 1: ...ABB machinery drives Hardware manual ACS850 04 drive modules 160 to 560 kW 200 to 700 hp ...
Page 4: ......
Page 12: ...Table of contents 12 ...
Page 20: ...Safety instructions 20 ...
Page 26: ...Introduction to the manual 26 ...
Page 81: ...Installation 81 Assembly drawing frame G1 3AUA0000132078 ...
Page 82: ...Installation 82 Assembly drawing frame G2 3AUA0000132062 ...
Page 83: ...Installation 83 Assembly drawing air baffles 3AUA0000132062 ...
Page 92: ...Installation 92 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Page 112: ...Installation checklist 112 ...
Page 114: ...Start up 114 ...
Page 116: ...Fault tracing 116 ...
Page 140: ...Technical data 140 ...
Page 142: ...Dimension drawings 142 Frame G1 Drive module dimensions ...
Page 143: ...Dimension drawings 143 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Page 144: ...Dimension drawings 144 ...
Page 145: ...Dimension drawings 145 Frame G1 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Page 146: ...Dimension drawings 146 Frame G2 Drive module dimensions ...
Page 147: ...Dimension drawings 147 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Page 148: ...Dimension drawings 148 ...
Page 149: ...Dimension drawings 149 Frame G2 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Page 150: ...Dimension drawings 150 Frames G1 and G2 Bottom plate 3AUA0000082240 ...
Page 151: ...Dimension drawings 151 Frames G1 and G2 Air baffles 3AUA0000138986 ...
Page 152: ...Dimension drawings 152 ...
Page 162: ...du dt filters 162 ...
Page 164: ...3AUA0000081249 Rev C EN 2013 04 11 Contact us www abb com drives www abb com drivespartners ...