Installation
104
Default I/O connection diagram
Notes:
[…] denotes default setting with ACS850
Standard Control Program (Factory
macro). See the firmware manual for other
macros.
*Total maximum current: 200 mA
The wiring shown is for demonstrative
purposes only. Further information of the
usage of the connectors and jumpers are
given in the text; see also chapter
.
Wire sizes and tightening torques:
XPOW, XRO1, XRO2, XRO3, XD24:
0.5 … 2.5 mm
2
(24…12 AWG). Torque:
0.5 N·m (5 lbf·in)
XDI, XDIO, XAI, XAO, XD2D, XSTO:
0.5 … 1.5 mm
2
(28…14 AWG). Torque:
0.3 N·m (3 lbf·in)
XPOW
External power input
24 V DC, 1.6 A
+24VI
1
GND
2
XRO1, XRO2, XRO3
Relay output RO1 [Ready]
250 V AC / 30 V DC
2 A
NO
1
COM
2
NC
3
Relay output RO2 [Modulating]
250 V AC / 30 V DC
2 A
NO
4
COM
5
NC
6
Relay output RO3 [Fault(-1)]
250 V AC / 30 V DC
2 A
NO
7
COM
8
NC
9
XD24
+24 V DC*
+24VD
1
Digital input ground
DIGND
2
+24 V DC*
+24VD
3
Digital input/output ground
DIOGND
4
Ground selection jumper
AI1
XDI
Digital input DI1 [Stop/Start]
DI1
1
Digital input DI2
DI2
2
Digital input DI3 [Reset]
DI3
3
Digital input DI4
DI4
4
Digital input DI5
DI5
5
Digital input DI6 or thermistor input
DI6
6
Start interlock (0 = Stop)
DIIL
A
XDIO
Digital input/output DIO1 [Output: Ready]
DIO1
1
Digital input/output DIO2 [Output: Running]
DIO2
2
XAI
Reference voltage (+)
+VREF
1
Reference voltage (–)
-VREF
2
Ground
AGND
3
Analog input AI1 (Current or voltage, selectable by jumper AI1) [Speed
reference 1]
AI1+
4
AI1-
5
Analog input AI2 (Current or voltage, selectable by jumper AI2)
AI2+
6
AI2-
7
AI1 current/voltage selection jumper
AI1
AI2 current/voltage selection jumper
AI2
XAO
Analog output AO1 [Current %]
AO1+
1
AO1-
2
Analog output AO2 [Speed %]
AO2+
3
AO2-
4
XD2D
Drive-to-drive link termination jumper
T
Drive-to-drive link.
B
1
A
2
BGND
3
XSTO
Safe torque off. Both circuits must be closed for the drive to start.
OUT1
1
OUT2
2
IN1
3
IN2
4
Control panel connection
Memory unit connection
XPOW
(2-pole, 2.5 mm
2
)
Order of terminal headers and
jumpers
XRO1
(3-pole, 2.5 mm
2
)
XRO2
(3-pole, 2.5 mm
2
)
XRO3
(3-pole, 2.5 mm
2
)
XD24
(4-pole, 2.5 mm
2
)
XDI
(7-pole, 1.5 mm
2
)
DI/DIO grounding selection
XDIO
(2-pole, 1.5 mm
2
)
XAI
(7-pole, 1.5 mm
2
)
AI1, AI2
XAO
(4-pole, 1.5 mm
2
)
XD2D
(3-pole, 1.5 mm
2
)
XSTO (orange)
(4-pole, 1.5 mm
2
)
T
Summary of Contents for ACS850-04 series
Page 1: ...ABB machinery drives Hardware manual ACS850 04 drive modules 160 to 560 kW 200 to 700 hp ...
Page 4: ......
Page 12: ...Table of contents 12 ...
Page 20: ...Safety instructions 20 ...
Page 26: ...Introduction to the manual 26 ...
Page 81: ...Installation 81 Assembly drawing frame G1 3AUA0000132078 ...
Page 82: ...Installation 82 Assembly drawing frame G2 3AUA0000132062 ...
Page 83: ...Installation 83 Assembly drawing air baffles 3AUA0000132062 ...
Page 92: ...Installation 92 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Page 112: ...Installation checklist 112 ...
Page 114: ...Start up 114 ...
Page 116: ...Fault tracing 116 ...
Page 140: ...Technical data 140 ...
Page 142: ...Dimension drawings 142 Frame G1 Drive module dimensions ...
Page 143: ...Dimension drawings 143 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Page 144: ...Dimension drawings 144 ...
Page 145: ...Dimension drawings 145 Frame G1 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Page 146: ...Dimension drawings 146 Frame G2 Drive module dimensions ...
Page 147: ...Dimension drawings 147 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Page 148: ...Dimension drawings 148 ...
Page 149: ...Dimension drawings 149 Frame G2 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Page 150: ...Dimension drawings 150 Frames G1 and G2 Bottom plate 3AUA0000082240 ...
Page 151: ...Dimension drawings 151 Frames G1 and G2 Air baffles 3AUA0000138986 ...
Page 152: ...Dimension drawings 152 ...
Page 162: ...du dt filters 162 ...
Page 164: ...3AUA0000081249 Rev C EN 2013 04 11 Contact us www abb com drives www abb com drivespartners ...