Technical data
129
Losses, cooling data and noise
Terminal and lead-through data for the power cables
The maximum accepted cable size is 4 × (3 × 240) mm
2
or 4 × (3 × 500 AWG).
Screw size for connecting busbars to the drive module input and output busbars:
M12, tightening torque 50...75 N·m.
Units with optional common mode filter (+E208)
The additional busbars are included in the delivery of units with optional common
mode filter (+E208). The output busbars of the drive module can be enhanced with
the additional busbars in units without optional cabling panels (no +H381 or +H383).
Then, the maximum accepted cable size is 4 × (3 × 240) mm
2
or 4 × (3 × 500 AWG).
Screw size for connecting busbars to the drive module input and output busbars:
M12, tightening torque 50...75 N·m.
Units with optional cabling panels (+H381 or +H383)
The maximum accepted cable size is 4 × (3 × 240) mm
2
or 4 × (3 × 500 AWG). The
cabling panels are connected to the drive module busbars with M12 serpress nuts,
tightening torque 30 N·m (20 lbf·ft).
Input, motor and brake resistor cable terminal sizes and tightening torques are given
below.
Two-hole 1/2 inch diameter cable lugs can be used.
Drive type
ACS850-04
Frame
size
Air flow
Heat dissipation
Noise
m
3
/h
ft
3
/min
W
dB(A)
-387A-5
G1
1200
707
4403
72
-500A-5
G1
1200
707
5602
72
-580A-5
G1
1200
707
6409
72
-650A-5
G1
1200
707
8122
72
-710A-5
G2
1200
707
8764
72
-807A-5
G2
1200
707
9862
72
-875A-5
G2
1420
848
10578
71
U1, V1, W1, U2, V2, W2, UDC+, UDC-, R+, R-
Grounding busbar
Screw
Tightening torque
Screw
Tightening torque
N-m
N-m
M12
50...75
M10
30...44
U1, V1, W1, U2, V2, W2, UDC+, UDC-, R+, R-
Grounding busbar
Screw
Tightening torque
Screw
Tightening torque
lbf·ft
lbf·ft
1/2
37...55
3/8
22...32
Summary of Contents for ACS850-04 series
Page 1: ...ABB machinery drives Hardware manual ACS850 04 drive modules 160 to 560 kW 200 to 700 hp ...
Page 4: ......
Page 12: ...Table of contents 12 ...
Page 20: ...Safety instructions 20 ...
Page 26: ...Introduction to the manual 26 ...
Page 81: ...Installation 81 Assembly drawing frame G1 3AUA0000132078 ...
Page 82: ...Installation 82 Assembly drawing frame G2 3AUA0000132062 ...
Page 83: ...Installation 83 Assembly drawing air baffles 3AUA0000132062 ...
Page 92: ...Installation 92 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Page 112: ...Installation checklist 112 ...
Page 114: ...Start up 114 ...
Page 116: ...Fault tracing 116 ...
Page 140: ...Technical data 140 ...
Page 142: ...Dimension drawings 142 Frame G1 Drive module dimensions ...
Page 143: ...Dimension drawings 143 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Page 144: ...Dimension drawings 144 ...
Page 145: ...Dimension drawings 145 Frame G1 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Page 146: ...Dimension drawings 146 Frame G2 Drive module dimensions ...
Page 147: ...Dimension drawings 147 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Page 148: ...Dimension drawings 148 ...
Page 149: ...Dimension drawings 149 Frame G2 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Page 150: ...Dimension drawings 150 Frames G1 and G2 Bottom plate 3AUA0000082240 ...
Page 151: ...Dimension drawings 151 Frames G1 and G2 Air baffles 3AUA0000138986 ...
Page 152: ...Dimension drawings 152 ...
Page 162: ...du dt filters 162 ...
Page 164: ...3AUA0000081249 Rev C EN 2013 04 11 Contact us www abb com drives www abb com drivespartners ...