Technical data
90
Cable types
The table below gives copper and aluminium cable types for different load currents.
Cable sizing is based on max. 9 cables laid on a cable ladder side by side, ambient
temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and
IEC 60364-5-2/2001). For other conditions, size the cables according to local safety
regulations, appropriate input voltage and the load current of the drive.
Cable entries
Mains, DC link and motor cable terminal sizes (per phase), accepted cable
diameters and tightening torques are given below
.
* with cable lugs 16...70 mm
2
, tightening torque 20...40 Nm
Dimensions, weights and noise
Copper cables with concentric
copper shield
Aluminium cables with concentric
copper shield
Max. load
current
A
Cable type
mm
2
Max. load
current
A
Cable type
mm
2
34
3x6
61
3x25
47
3x10
75
3x35
62
3x16
91
3x50
79
3x25
117
3x70
98
3x35
143
3x95
119
3x50
165
3x120
153
3x70
191
3x150
186
3x95
215
3x120
249
3x150
284
3x185
PDM code: 00096931-C
Frame size
U1, V1, W1, U2, V2, W2, UDC+,UDC
-
Earthing PE
Wire size
Max. cable Ø
IP 21
Tightening
torque
Wire size
Tightening
torque
mm
2
mm
Nm
mm
2
Nm
R5
16…70
35
10
16…70
15
R6
95...185 *
53
20…40
95
8
Frame size
IP 21
Noise
Height
Width
Depth
Weight
mm
mm
mm
kg
dB
R5
816
265
390
65
70
R6
970
300
439
100
73
Summary of Contents for ACS800-11
Page 1: ...ACS800 Hardware Manual ACS800 11 Drives 5 5 to 110 kW ACS800 U11 Drives 7 5 to 125 HP ...
Page 4: ......
Page 12: ...Safety instructions 12 ...
Page 30: ...The ACS800 11 U11 30 ...
Page 36: ...Mechanical installation 36 ...
Page 54: ...Planning the electrical installation 54 ...
Page 74: ...Installation checklist 74 ...
Page 84: ...Operation 84 ...
Page 104: ...Technical data 102 ...
Page 108: ...Dimensional drawings 106 ...
Page 111: ...External 24 V power supply for the RMIO board 109 5 6 7 8 ...
Page 112: ...External 24 V power supply for the RMIO board 110 ...
Page 113: ......