Planning the electrical installation
47
Alternative power cable types
Power cable types that can be used with the drive are represented below.
Motor cable shield
To effectively suppress radiated and conducted radio-frequency emissions, the
shield conductivity must be at least 1/10 of the phase conductor conductivity. The
requirements are easily met with a copper or aluminium shield. The minimum
requirement of the motor cable shield of the drive is shown below. It consists of a
concentric layer of copper wires with an open helix of copper tape. The better and
tighter the shield, the lower the emission level and bearing currents.
Symmetrical shielded cable: three phase conductors
and a concentric or otherwise symmetrically
constructed PE conductor, and a shield
Recommended
PE conductor
and shield
Shield
Shield
A separate PE conductor is required if the conductivity
of the cable shield is < 50 % of the conductivity of the
phase conductor.
A four-conductor system:
three phase conductors
and a protective
conductor.
Shield
PE
PE
PE
Not allowed for motor cables
with phase
conductor cross section larger than 10 mm
2
[motors > 30 kW (40 HP)].
Not allowed for motor cables
Insulation jacket
Copper wire screen
Helix of copper tape
Cable core
Inner insulation
Summary of Contents for ACS800-11
Page 1: ...ACS800 Hardware Manual ACS800 11 Drives 5 5 to 110 kW ACS800 U11 Drives 7 5 to 125 HP ...
Page 4: ......
Page 12: ...Safety instructions 12 ...
Page 30: ...The ACS800 11 U11 30 ...
Page 36: ...Mechanical installation 36 ...
Page 54: ...Planning the electrical installation 54 ...
Page 74: ...Installation checklist 74 ...
Page 84: ...Operation 84 ...
Page 104: ...Technical data 102 ...
Page 108: ...Dimensional drawings 106 ...
Page 111: ...External 24 V power supply for the RMIO board 109 5 6 7 8 ...
Page 112: ...External 24 V power supply for the RMIO board 110 ...
Page 113: ......