Installation checklist
73
Installation checklist
Checklist
Check the mechanical and electrical installation of the drive before start-up. Go
through the checklist below together with another person. Read the
on the first pages of this manual before you work on the unit.
Check
MECHANICAL INSTALLATION
The ambient operating conditions are allowed. (See
Mechanical installation, Technical data
or US tables /
The unit is fixed properly on a vertical non-flammable wall. (See
)
The cooling air will flow freely.
The motor and the driven equipment are ready for start. (See
installation: Motor selection and compatibility, Technical data
:
ELECTRICAL INSTALLATION
Planning the electrical installation, Electrical installation.
)
The +E202 and +E200 EMC filter capacitors are disconnected if the drive is connected to an
IT (ungrounded) system.
The capacitors are reformed if stored over one year (refer to
ACS 600/800 Capacitor
Reforming Guide
[64059629 (English)].
The drive is grounded properly.
The mains (input power) voltage matches the drive nominal input voltage.
The mains (input power) connections at U1, V1 and W1 and their tightening torques are OK.
Appropriate mains (input power) fuses and disconnector are installed.
The motor connections at U2, V2 and W2 and their tightening torques are OK.
The motor cable is routed away from other cables.
There are no power factor compensation capacitors in the motor cable.
The external control connections inside the drive are OK.
There are no tools, foreign objects or dust from drilling inside the drive.
Mains (input power) voltage cannot be applied to the output of the drive (with bypass
connection).
Drive, motor connection box and other covers are in place.
Summary of Contents for ACS800-11
Page 1: ...ACS800 Hardware Manual ACS800 11 Drives 5 5 to 110 kW ACS800 U11 Drives 7 5 to 125 HP ...
Page 4: ......
Page 12: ...Safety instructions 12 ...
Page 30: ...The ACS800 11 U11 30 ...
Page 36: ...Mechanical installation 36 ...
Page 54: ...Planning the electrical installation 54 ...
Page 74: ...Installation checklist 74 ...
Page 84: ...Operation 84 ...
Page 104: ...Technical data 102 ...
Page 108: ...Dimensional drawings 106 ...
Page 111: ...External 24 V power supply for the RMIO board 109 5 6 7 8 ...
Page 112: ...External 24 V power supply for the RMIO board 110 ...
Page 113: ......