Technical data
99
Input cable fuses
The ratings of UL listed fuses for branch circuit protection are listed below. The fuses
also prevent damage to the adjoining equipment of the drive in case of a short-circuit
inside the drive.
Check that the operating time of the fuse is below 0.5 seconds
.
The operating time depends on the supply network impedance and the cross-
sectional area and length of the supply cable. The fuses must be of the “non-time
delay” type. See also
Planning the electrical installation
.
Note 1: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 2:
Larger fuses must not be used.
Note 3:
Fuses from other manufacturers can be used if they meet the ratings.
ACS800-U11 type
ACS800-11 type
Input
current
Fuse
A
A
V
Manufacturer
Type
UL class
Three-phase supply voltage 208 V, 220 V,
230 V
or 240 V
-0011-2
32
40
600
Bussmann
JJS-40
T
-0016-2
44
70
600
Bussmann
JJS-70
T
-0020-2
55
80
600
Bussmann
JJS-80
T
-0025-2
70
90
600
Bussmann
JJS-90
T
-0030-2
82
100
600
Bussmann
JJS-100
T
-0040-2
112
150
600
Bussmann
JJS-150
T
-0050-2
140
200
600
Bussmann
JJS-200
T
-0060-2
157
200
600
Bussmann
JJS-200
T
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V,
460
V
, 480 V or 500 V
-0020-5
29
40
600
Bussmann
JJS-40
T
-0025-5
33
50
600
Bussmann
JJS-50
T
-0030-5
44
70
600
Bussmann
JJS-70
T
-0040-5
54
80
600
Bussmann
JJS-80
T
-0050-5
65
90
600
Bussmann
JJS-90
T
-0060-5
76
100
600
Bussmann
JJS-100
T
-0070-5
112
150
600
Bussmann
JJS-150
T
-0100-5
129
200
600
Bussmann
JJS-200
T
-0120-5
145
200
600
Bussmann
JJS-200
T
PDM code: 00317419-C
Summary of Contents for ACS800-11
Page 1: ...ACS800 Hardware Manual ACS800 11 Drives 5 5 to 110 kW ACS800 U11 Drives 7 5 to 125 HP ...
Page 4: ......
Page 12: ...Safety instructions 12 ...
Page 30: ...The ACS800 11 U11 30 ...
Page 36: ...Mechanical installation 36 ...
Page 54: ...Planning the electrical installation 54 ...
Page 74: ...Installation checklist 74 ...
Page 84: ...Operation 84 ...
Page 104: ...Technical data 102 ...
Page 108: ...Dimensional drawings 106 ...