Electrical installation
60
Frame size R6: Cable terminal installation [95 to 185 mm
2
(3/0 to 350 AWG)] cables
Frame sizes R6: Cable lug installation [16 to 70 mm
2
(6 to 2/0 AWG) cables]
Isolate the ends of
the cable lugs with
insulating tape or
shrink tubing.
5
5
a. Connect the cable to the terminal.
b. Connect the terminal to the drive.
WARNING!
If the wire size is less than
95 mm
2
(3/0 AWG), a cable lug must
be used. A cable of wire size less than
95 mm
2
(3/0 AWG) connected to this
terminal will loosen and may damage
the drive.
a
b
5
5
6
PE
6
PE
Remove the cable terminals.
Fasten the cable lugs with screws.
Shroud on the cable terminals (cable terminal
installation)
9
9