Technical data
100
Cable types
Cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or
earth (directly buried). For other conditions, dimension the cables according to local safety regulations,
appropriate input voltage and the load current of the drive.
Cable Entries
Brake resistor, input and motor cable (per phase) terminal sizes, accepted cable
diameters and tightening torques are given below
.
* with cable lugs 6...2/0 AWG, tightening torque 14.8...29.5 lbf ft
Dimensions and weights
Copper cables with concentric copper shield
Max. load
current
A
Cable type
AWG/kcmil
31
10
44
8
57
6
75
4
88
3
101
2
114
1
132
1/0
154
2/0
176
3/0
202
4/0
224
250 MCM or 2 x 1
251
300 MCM or 2 x 1/0
273
350 MCM or 2 x 2/0
PDM code: 00096931-C
Frame size
U1, V1, W1, U2, V2, W2, UDC+, UDC-
Grounding PE
Wire size
Wire Ø
(UL type 1)
Tightening
torque
Wire size
Tightening
torque
AWG
in.
lbf ft
AWG
lbf ft
R5
4...2/0 1.39
11.1
4...2/0 11.1
R6
3/0 ... 350 MCM *
2.09
14.8...29.5
4/0
5.9
Frame size
UL type 1
Height
Width
Depth
Weight
in.
in.
in.
lb
R5
32.03
10.43
15.35
143
R6
38.19
11.81
17.28
220
Summary of Contents for ACS800-11
Page 1: ...ACS800 Hardware Manual ACS800 11 Drives 5 5 to 110 kW ACS800 U11 Drives 7 5 to 125 HP ...
Page 4: ......
Page 12: ...Safety instructions 12 ...
Page 30: ...The ACS800 11 U11 30 ...
Page 36: ...Mechanical installation 36 ...
Page 54: ...Planning the electrical installation 54 ...
Page 74: ...Installation checklist 74 ...
Page 84: ...Operation 84 ...
Page 104: ...Technical data 102 ...
Page 108: ...Dimensional drawings 106 ...
Page 111: ...External 24 V power supply for the RMIO board 109 5 6 7 8 ...
Page 112: ...External 24 V power supply for the RMIO board 110 ...
Page 113: ......