Planning the electrical installation
52
Connection of a motor temperature sensor to the drive I/O
WARNING!
IEC 60664 requires double or reinforced insulation between live parts
and the surface of accessible parts of electrical equipment which are either non-
conductive or conductive but not connected to the protective earth.
To fulfil this requirement, the connection of a thermistor (and other similar
components) to the digital inputs of the drive can be implemented in three alternate
ways:
1. There is double or reinforced insulation between the thermistor and live parts of
the motor.
2. Circuits connected to all digital and analogue inputs of the drive are protected
against contact and insulated with basic insulation (the same voltage level as the
drive main circuit) from other low voltage circuits.
3. An external thermistor relay is used. The insulation of the relay must be rated for
the same voltage level as the main circuit of the drive. For connection, see
ACS800 Firmware Manual
.
Routing the cables
Route the motor cable away from other cable routes. Motor cables of several drives
can be run in parallel installed next to each other. It is recommended that the motor
cable, input power cable and control cables be installed on separate trays. Avoid
long parallel runs of motor cables with other cables in order to decrease
electromagnetic interference caused by the rapid changes in the drive output
voltage.
Where control cables must cross power cables make sure they are arranged at an
angle as near to 90 degrees as possible. Do not run extra cables through the drive.
The cable trays must have good electrical bonding to each other and to the
grounding electrodes. Aluminium tray systems can be used to improve local
equalizing of potential.
Summary of Contents for ACS800-11
Page 1: ...ACS800 Hardware Manual ACS800 11 Drives 5 5 to 110 kW ACS800 U11 Drives 7 5 to 125 HP ...
Page 4: ......
Page 12: ...Safety instructions 12 ...
Page 30: ...The ACS800 11 U11 30 ...
Page 36: ...Mechanical installation 36 ...
Page 54: ...Planning the electrical installation 54 ...
Page 74: ...Installation checklist 74 ...
Page 84: ...Operation 84 ...
Page 104: ...Technical data 102 ...
Page 108: ...Dimensional drawings 106 ...
Page 111: ...External 24 V power supply for the RMIO board 109 5 6 7 8 ...
Page 112: ...External 24 V power supply for the RMIO board 110 ...
Page 113: ......