Mechanical installation 13
4
Mechanical installation
Safety
All installation work must be carried out by qualified personnel according to the site and
equipment requirements and in compliance with the local regulations.
Examining the installation site
The installation site is sufficiently ventilated or cooled to transfer away the drive losses.
The maximum heat losses and cooling air flow are listed in ACS580MV outline drawing.
The ambient conditions of the drive shall not be higher than 40°C during operation of the
drive. In case the temperature out of the scope, contact ABB to get support.
ACS580MV can be installed using one of the four following cooling solutions:
•
Air conditioner solution (Recommanded)
•
Air duct solution
•
Fresh air circulation solution
•
Air-to-water heat exchanger solution