28 Installation checklist
Electrical installation
Door interlocking
Main circuit breaker (MCB)
1. Types and cross-sections of control cables suitable for the signal type and signal level
2. Types and cross-sections of power cables selected according to the
ACS580MV Engineering
Guideline
3. Pulse encoder cable screens connected to
screen grounding point
and not connected directly
to the pulse encoder interface (only applicable for drives with pulse encoder interface)
4. Internal cabling to integrated transformer (power, auxiliary, control and heater cables) made
according to the instructions in this manual (Chapter
Electrical installation
)
5. Cable entry made according to the instructions in this manual (Chapter
Electrical installation
)
6. All control cable screens and conductors are connected according to the instructions in this
manual (Chapter
Electrical installation
)
, appropriately labeled, and the customer-side
connections are completed
7. Heating cable (if supplied) installed according to the instructions in this manual (Chapter
Electrical installation
)
8. Ground cable of drive securely connected at both ends
9. Input and motor cables not connected at both ends (cables must be meggered before
connection, drive optional - recommended in case of long storage time, humid environment or
visible transportation damages)
1. Door locks tested and in operation
2. The manual release of the door safety switch(es) is in the
locked
position.
1.
Type of MCB selected as per
ACS580MV Engineering Guideline
2.
High voltage connections completed
3.
MCB ready to be tested with drive
Summary of Contents for ACS580MV
Page 1: ...ABB industrial drives ACS580MV Quick guide...
Page 4: ......
Page 8: ...8 Safety instructions...
Page 12: ...12 Lifting and transportation...
Page 21: ...Electrical installation 21 2 2 3 1 1...
Page 40: ...40 Fault tracing...
Page 44: ...www abb com drives www abb com drivespartners 2UBB019170 E01 Rev A EN 2018 03 15 Contact us...