54 Actual signals and parameters
30 FAULT
FUNCTIONS
Programmable protection functions
3010
STALL
FUNCTION
Selects how the drive reacts to a motor stall condition.
The protection is active if the drive has operated in a
stall region (see the figure below) longer than the time
set by parameter
In vector control the user defined limit = 2017 MAX
TORQUE 1 / 2018 MAX TORQUE 2 (applies for
positive and negative torques). See ACS355 User’s
manual (3AUA0000066143 [English]).
In scalar control the user defined limit = 2003 MAX
CURRENT. See ACS355 User’s manual
(3AUA0000066143 [English]).
The control mode is selected by parameter
.
FAULT
NOT SEL
Protection is inactive.
0
FAULT
The drive trips on fault MOTOR STALL (0012) and the
motor coasts to stop. See ACS355 User’s manual
(3AUA0000066143 [English]).
1
ALARM
The drive generates alarm MOTOR STALL (2012).
See ACS355 User’s manual (3AUA0000066143
[English]).
2
3011
STALL
FREQUENCY
Defines the frequency limit for stall function. See
parameter
.
10.0 Hz
0.5...50.0 Hz
Frequency
1 = 0.1 Hz
3012
STALL TIME
Defines the time for stall function. See parameter
10 s
10...400 s
Time
1 = 1 s
3026
POWER FAIL
START
Selects how the drive reacts when the control board is
externally powered by the MPOW-01 auxiliary power
extension module (see Appendix: Extension modules
in ACS355 User’s manual (3AUA0000066143
[English]) and start is requested by the user.
Note
: Only FAULT selection is available.
FAULT
FAULT
The drive trips on fault 0006 DC UNDERVOLT (See
ACS355 User’s manual (3AUA0000066143 [English]).
2
All parameters
No.
Name/
Value
Description
Def/ FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives Supplement ACS355 Solar pump inverter N827...
Page 4: ......
Page 10: ...10 Safety...
Page 14: ...14 Introduction...
Page 18: ...18 Operating principle and hardware description...
Page 30: ...30 Start up and controls...
Page 36: ...36 Program features...
Page 66: ...66 Actual signals and parameters...
Page 70: ...70 Fault tracing...
Page 76: ...76 Technical data...