Actual signals and parameters 45
AI1/JOYST
Analog input AI1 as joystick. At maximum reference,
the
• minimum input signal runs the motor in reverse
direction.
• maximum input signal runs the motor in forward
direction.
The minimum and maximum references are defined by
parameters 1104 REF1 MIN and 1105 REF1 MAX,
Note
: To control direction, set the parameter
= REQUEST
WARNING!
If parameter 1301 MINIMUM AI1 is
set to 0 V and analog signal is lost (0 V), the
rotation of the motor is reversed to the
maximum reference.
Set the following parameters to activate a fault when
analog input signal is lost:
• 1301 MINIMUM AI1 = 20% (2 V or 4 mA).
• 3021 AI1 FAULT LIMIT = 5% or higher.
• 3001 AI<MIN FUNCTION> = FAULT.
For parameter details, see
ACS355 User’s manual
(3AUA0000066143[English]
).
3
AI2/JOYST
See select AI1/JOYST.
4
DI3U,4D(R)
Digital input DI3: Reference increase.
Digital input DI4: Reference decrease.
Stop command resets the reference to zero.
Parameter 2205 ACCELER TIME 2 defines the rate of
reference change.
5
All parameters
No.
Name/
Value
Description
Def/ FbEq
Speed ref
(REF1)
Par. 1301 = 20%, par 1302 = 100%
1105
1104
0
-1104
-1105
2 V/4 mA
6
10 V/20 mA
AI1
1104
-1104
-2%
+2%
Hysteresis 4%
of full scale
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives Supplement ACS355 Solar pump inverter N827...
Page 4: ......
Page 10: ...10 Safety...
Page 14: ...14 Introduction...
Page 18: ...18 Operating principle and hardware description...
Page 30: ...30 Start up and controls...
Page 36: ...36 Program features...
Page 66: ...66 Actual signals and parameters...
Page 70: ...70 Fault tracing...
Page 76: ...76 Technical data...