Start-up and controls 29
Setting inverter reset time
1
Select parameter 6019
FAULT RESET TIME with the
UP/DOWN keys. Press EDIT
to change the parameter
value.
You can set the auto reset
time to start the inverter after
it has tripped in the event of
under-voltage fault, PV cell
maximum voltage fault or
when actual speed decreases
below the minimum motor
speed limit.
2
Press the UP/DOWN keys to
change the parameter value.
Press SAVE to store the
modified value or press
CANCEL to leave the set
mode. Any modifications not
saved are cancelled.
Step
Description
Keys
Control panel
R E M
P A R A M E T E R S
6017 DRY RUN TRP TIME
6018 DRY RUN RST TIME
6016 MIN LOAD CURRENT
E X I T
E D I T
00:00
6019 FAULT RESET TIME
2 min
R E M
P A R E D I T
6019 FAULT RESET TIME
2 min
C A N C E L
S A V E
00:00