26 Start-up and controls
To select auto/manual mode in the control panel, follow these steps:
Step
Description
Keys
Control panel
1
Press MENU to go to the main
menu.
2
Select PARAMETERS with the
UP/DOWN keys and press
ENTER.
3
Select 60 PUMP CONTROL
with the UP/DOWN keys and
press SEL.
4
Select the parameter 6001
AUTO/MANUAL SEL with the
UP/DOWN keys. Press EDIT
to change the parameter value.
5
Press the UP/DOWN keys to
change the parameter value.
For more details, see
parameter
.
Note
: MANUAL is the default
selection.
R E M
0r p m
D I R
M E N U
0.0 Hz
0.0 A
0.0 %
00:00
R E M
M A I N M E N U
PARAMETERS
ASSISTANTS
CHANGED PAR
E X I T
E N T E R
00:00
1
R E M
P A R G R O U P S
60 PUMP CONTROL
98 OPTIONS
99 START-UP DATA
60
E X I T
S E L
00:00
01 OPERATING DATA
61 FLOW CALCULATION
R E M
P A R A M E T E R S
6004 PV CELL MIN VOLT
6003 START DC VOLT
6002 MANUAL START CMD
6001 AUTO/MANUAL SEL
MANUAL
E X I T
E D I T
00:00
R E M
P A R E D I T
6001 AUTO/MANUAL SEL
MANUAL
C A N C E L
S A V E
00:00
[ 1 ]