CHAPTER 6 – ELECTRICAL INSTALLATION
104
6. Remove the cable insulation at the point of
entry
(1)
.
If the outer cable screen is non-conductive, cut
open the cable screen in the middle of the
stripped area
(1)
. To turn the conductive side
inside out, pull the cable screen ends over the
cable insulation
(2)
. Connect the screens ends
with a continuous conducting foil
(3)
.
7. Pull the cables through the EMC cushions.
8. Push the cushions together so they fit tightly
around the bare screen and tighten the screws.