CHAPTER 10 – PREVENTIVE AND CORRECTIVE MAINTENANCE
170
10.6.5 Connecting a grounding set
1. Connect the enclosure ground clamp
to the ground ball stud of the cabinet’s ground-
ing frame.
2. Use the telescopic insulating pole to connect
the busbar ground clamps
(10-10: 2)
to the
ground ball studs of the busbars, and to tighten
each connection.
Connect the inner most busbar first
(10-10: 3)
,
then the middle busbar
(10-10: 4)
and then the
outer busbar
.
The drive is now dead, and safe access is possible.
—