61
ACS2000 AFE 2MVA UM
3BHS355653 ZAB E01 REV. H
—
Table 3-7
Example for digital input signal allocation
Terminal
Channel
Default setting
Par. group
X11-1
DI01
External start / stop request
72.06 – 72.09
X11-2
Common
X11-3
DI02
Forward / reverse
72.10 – 72.11
X11-4
Common
X11-5
DI03
Freely programmable
—
X11-6
Common
X11-7
DI04
Ramp 1 / 2
72.41 – 72.42
X11-8
Common
X11-9
DI05
Ext1 / Ext2
30 – 31
X11-10
Common
X12-1
DI06
Constant speed select
24 – 25
X12-2
Common
X12-3
DI07
External ON request (start DC link charge)
72.02 – 72.03
X12-4
Common
X12-5
DI08
Process stop (stops drive)
72.43 – 72.44
X12-6
Common
X12-7
DI09
MV switchgear open
*
X12-8
Common
X12-9
DI10
MV switchgear closed
*
X12-10
Common
X13-1
DI11
MV switchgear available (not tripped)
*
X13-2
Common
X13-3
DI12
Remote reset
72.33 – 72.34
X13-4
Common
X13-5
DI13
External OFF request
72.04 – 72.05
X13-6
Common
X13-7
DI14
Disable local operation
72.35 – 72.36
X13-8
Common
X13-9
+24 V
+0 V
24 V control logic
—
X13-10
Common
* Not configurable
Summary of Contents for ACS2000 AFE 2MVA
Page 8: ...General information on manual and equipment ...
Page 13: ...13 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 14: ...Terms abbreviations trademarks ...
Page 19: ...19 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 20: ...Important note on main circuit breaker ...
Page 48: ...Chapter 3 Control system 49 Control unit 50 Main components 55 I O interfaces ...
Page 69: ...69 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 111: ...111 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 118: ...Commissioning check list ...
Page 153: ...153 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 180: ......