5.3 General notes on installation
NOTICE
Foreign matter and particularly metallic dust can
cause failure and damage when the drive is ener
-
gized.
Ensure that foreign matter cannot enter the
cabinet:
• Close the doors and cover openings completely
when work is discontinued.
• Retrieve any foreign matter which accidentally
dropped into the cabinet.
5.3.1 Dimensions, clearances
5.3.2 Cabinet roof
The cabinet roof is not designed as a mounting
base for foreign devices, cable ducts etc. There-
fore, it is not permitted to install any foreign
device on the roof.
5.3.3 Fire protection
Suitable fire protection measures should be
applied to prevent fire spreading into the drive.
5.3.4 Cable duct material
Cable ducts should be of non-flammable material
with a non-abrasive surface.
All cable entries and exits should be protected to
prevent dust, humidity and animals entering the
drive.
5.3.5 Preparing the floor
Condition of the floor
• Must support the weight of the cabinet
• Overall incline across 5 m must not exceed 5
mm
• Even
• Non-flammable, smooth and non- abrasive
• Protected against humidity diffusion
!
For information on cabinet dimensions,
clearances to be observed and mounting
hole sizes, see
Appendix C – Mechanical
drawings
.
Summary of Contents for ACS2000 AFE 2MVA
Page 8: ...General information on manual and equipment ...
Page 13: ...13 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 14: ...Terms abbreviations trademarks ...
Page 19: ...19 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 20: ...Important note on main circuit breaker ...
Page 48: ...Chapter 3 Control system 49 Control unit 50 Main components 55 I O interfaces ...
Page 69: ...69 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 111: ...111 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 118: ...Commissioning check list ...
Page 153: ...153 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 180: ......