133
ACS2000 AFE 2MVA UM
3BHS355653 ZAB E01 REV. H
Each time the auxiliary voltage is switched off and
on again, the emergency-off safety relay of the
drive is actuated and lets the EMERGENCY RESET
pushbutton flashes.
The EMERGENCY RESET pushbutton also flashes if
the EMERGENCY OFF pushbutton on the control
compartment door, or any other emergency-off
switch linked to the drive, is pressed. If the EMER-
GENCY RESET pushbutton continuous flashing,
verify that there is no emergency-off command
active.
For further information, see
4. Check that no alarm or fault messages are dis-
played on the CDP control panel.
When a fault message is displayed on the CDP
control panel, reset the fault.
If a fault cannot be reset, it must be rectified by
the responsible personnel.
See
for further
information.
When no alarms and faults are present and the
drive is ready, the CDP control panel displays
ReadyOn
.
5. Press the
SUPPLY ON pushbutton
on the con-
trol compartment door to close the MCB and
charge the DC link. The
pushbutton lights up.
The status line of the CDP control panel alter-
nates between
Charging
and
AuxiliaryOn
.
After charging has been finished,
the AFE starts
to modulate.
If the CDP control panel was switched to the
AFE, you would first see the message
Modu-
lating
and then after a short instant the
message
ReadyRef
in the status line of the
display.
When the AFE is in
ReadyRef
state, the state of
the INU changes to
ReadyRun
and
the motor
can be started.
6. Enter the reference value.
For further information, see
7. Start the motor.
After the motor has been magnetized, the
motor speed ramps up to the reference value.
While the motor is accelerating, the run status
message on the display blinks. When the motor
speed has reached the reference value, the run
status message lights up permanently.
To indicate that the drive is operating, the dis-
play shows
ReadyRef
:
1 L ->
0.0 rpm
StateINU
ReadyOn
MOTOR SP
0.00 rpm
POWER
0.0 kW
1 L ->
0.0 rpm
StateINU
Charging
MOTOR SP
0.00 rpm
POWER
0.0 kW
AuxiliaryOn
Charging
1 L ->
0.0 rpm 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
1 L ->
[600.0 rpm] 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
1 L ->
600.0 rpm
StateINU
ReadyRef
MOTOR SP
0.00 rpm
POWER
1000.0 kW
Summary of Contents for ACS2000 AFE 2MVA
Page 8: ...General information on manual and equipment ...
Page 13: ...13 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 14: ...Terms abbreviations trademarks ...
Page 19: ...19 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 20: ...Important note on main circuit breaker ...
Page 48: ...Chapter 3 Control system 49 Control unit 50 Main components 55 I O interfaces ...
Page 69: ...69 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 111: ...111 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 118: ...Commissioning check list ...
Page 153: ...153 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 180: ......