CHAPTER 10 – PREVENTIVE AND CORRECTIVE MAINTENANCE
164
SD
Off
No SD/SDHC card
Green
Card attached and taken into use
Blinking green
Card attached and initialization in progress
Yellow
Card can be safely removed
Blinking yellow
Card attached, removal in progress
Blinking yellow
Together with the blinking red STAT LED: System waits for confirmation of reboot
operation or network override
Red
Card error, for example write protection prevents from writing data to the card
Blinking red
Card initialization failed. Unsupported card type (eg, SDXC and MMC cards are not
supported).
PNL 1 /
PNL 2
Off
No devices (no wire) connected to the PNL port
Green
All devices connected, identified and commissioned
Blinking green
Manual or automatic discovery of devices in progress
Yellow
Communication OK, but device connectivity limited.
All devices are ready to be unplugged/disconnected.
Red
Communication error caused the panel port network initialization to fail.
Unknown device in the network, or something interfering the network and preventing
proper detection of monitored devices.
Blinking red
Unsupported device found in the network, or too many devices in the network to be
monitored
PC ETH 1
Off
PC not connected.
If an Ethernet cable is connected to the PC ETH 1 port but no one uses the NETA-21, the
LED remains blank.
Green
Connection set up and in operation, for example, DHCP is active and at least one PC
has got an IP-address
1/2-second
blinking green
NETA-21 provides IP addresses for local devices.
Activate the DHCP server mode by pressing the SD RJ45 button for
five seconds.
When a PC is connected and the NETA-21 has provided an IP address for it, the LED
turns steady green.
Note: The DHCP server functionality remains enabled until the NETA-21 is restarted or
until the DHCP server is disabled in the web UI.
1-second
blinking green
At least one user has been logged on to the user interface
Blinking yellow
Factory-level access/operation. Firmware update in progress.
Note: System status (STAT LED) blinks during the firmware update.
PWR
Off
Power off
Green
Power on
Yellow
Timed power off or standby.
NETA-21 can go to the standby mode as a protective measure (eg, if the environmental
temperature is too high).
To wake up the NETA-21, press the SD RJ45 button.
STAT
Green
System in operation, OK
Yellow
System starts up, services not yet fully operational
1/4-second
blinking yellow
System waits for a confirmation of the reboot operation or network override.
If you reboot the NETA-21 by pressing the reset button for 5 seconds when the NETA-
21 is running, the STAT LED starts blinking. Confirm the reboot operation by pressing
the SC RJ45 button. If you do not confirm the reboot operation, it stops after a 1-
minute delay.
You can override the network settings by pressing the SD RJ45 button for 10 seconds
when the NETA-21 powers up. If you keep pressing the button for about 20 seconds,
the STAT LED starts blinking, which indicates that you can release the button. If you do
not release the SD RJ45 button within one minute (or if the button is locked to the
“ON” position), the default network settings are not restored.
1-second
blinking yellow
Firmware update in progress
Blinking red
Error occurred during the start-up of the NETA-21.
If the start-up fails, the NETA-21 restarts itself automatically after a few seconds.
During the reboot operation, all LEDs excluding the PWR LED flash before the STAT
LED turns yellow again.
If the yellow STAT LED and blinking red STAT LED alternate and the STAT LED does not
turn green, the start-up of the NETA-21 fails continuously. Try resetting the NETA-21 to
factory settings
MON
Blinking green
NETA-21 sends data (eg, email) to an external destination.
Blinking red
NETA-21 fails to send data (eg, email) to an external destination.
—
Table 10-2
NETA-21 LED description
LED
Color
Meaning
Summary of Contents for ACS2000 AFE 2MVA
Page 8: ...General information on manual and equipment ...
Page 13: ...13 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 14: ...Terms abbreviations trademarks ...
Page 19: ...19 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 20: ...Important note on main circuit breaker ...
Page 48: ...Chapter 3 Control system 49 Control unit 50 Main components 55 I O interfaces ...
Page 69: ...69 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 111: ...111 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 118: ...Commissioning check list ...
Page 153: ...153 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Page 180: ......