Functional safety components
The mission time of functional safety components is 20 years which equals the
time during which failure rates of electronic components remain constant. This
applies to the components of the standard Safe torque off circuit as well as any
modules, relays and, typically, any other components that are part of functional
safety circuits.
The expiry of mission time terminates the certification and SIL/PL classification
of the safety function. The following options exist:
•
Renewal of the whole drive and all optional functional safety module(s) and
components.
•
Renewal of the components in the safety function circuit. In practice, this is
economical only with larger drives that have replaceable circuit boards and
other components such as relays.
Note that some of the components may already have been renewed earlier,
restarting their mission time. The remaining mission time of the whole circuit is
however determined by its oldest component.
Contact your local ABB service representative for more information.
Cleaning the heatsink
The drive module heatsink fins pick up dust from the cooling air. The drive runs
into overtemperature warnings and faults if the heatsink is not clean. When
necessary, clean the heatsink as follows.
WARNING!
Use the required personal protective equipment. Wear protective gloves and
long sleeves. Some parts have sharp edges.
WARNING!
Use a vacuum cleaner with antistatic hose and nozzle, and wear a grounding
wristband. Using a normal vacuum cleaner creates static discharges which
can damage circuit boards.
1.
Stop the drive and do the steps in section
before you start the work.
2.
Remove the module cooling fan(s). See the separate instructions.
3.
Blow dry, clean and oil-free compressed air from bottom to top and
simultaneously use a vacuum cleaner at the air outlet to trap the dust. If there
is a risk of dust entering adjoining equipment, do the cleaning in another room.
4. Reinstall the cooling fan.
Maintenance 87
Summary of Contents for ACS180-04S-03A7-1
Page 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Page 2: ......
Page 4: ......
Page 12: ...12...
Page 24: ...24...
Page 84: ...84...
Page 96: ...96...
Page 146: ...146...
Page 148: ...Frame R0 148 Dimension drawings...
Page 149: ...Frame R1 Dimension drawings 149...
Page 151: ...Frame R3 Dimension drawings 151...
Page 152: ...Frame R4 152 Dimension drawings...
Page 160: ...160...
Page 180: ...Declarations of conformity 180 The Safe torque off function...
Page 181: ...The Safe torque off function 181...
Page 182: ...182 The Safe torque off function...
Page 183: ...The Safe torque off function 183...
Page 184: ...184...
Page 187: ...Installation 1 2 N m M4x16 2x 3 3 3 2 2 2 2 Accessories 187...
Page 189: ...Installation 3 3 2 2 2 3 2 2 N m M4x16 4x 1 Accessories 189...