Network SC
1)
Miniature circuit breaker
Frame
ACS180-04...
kA
ABB type
5
S203P-Z63NA
R3
-033A-2
5
Contact ABB
R4
-048A-2
5
Contact ABB
R4
-055A-2
3-phase
Un = 380 ... 415V
5
S203P-B4
R0
-01A8-4
5
S203P-B6
R0
-02A6-4
5
S203P-B6
R0
-03A3-4
5
S203P-B8
R1
-04A0-4
5
S203P-B10
R1
-05A6-4
5
S203P-B16
R1
-07A2-4
5
S203P-B16
R1
-09A4-4
5
S203P-B25
R2
-12A6-4
5
S203P-B32
R2
-17A0-4
5
S203P-B50
R3
-25A0-4
5
S203P-B63
R3
-033A-4
5
S803S-B80
R4
-038A-4
5
S803-B100
R4
-045A-4
5
S803-B100
R4
-050A-4
1) Maximum permitted rated conditional short-circuit current (IEC 61800-5-1) of the electrical power
network.
■
Miniature circuit breakers (UL)
ACS180-04 drives are suitable for use on a circuit capable of delivering not more
than 10 kA symmetrical amperes (RMS) at 240 or 480Y/277 V maximum, when
protected by appropriate circuit breakers in the tables below. Additional fuse
protection is not required by UL when using circuit breakers herein. Circuit breakers
are not required to be in the same enclosure as the drive.
Minimum enclosure volume
2) 3)
Breaker type(UL)
1)
Frame
Type ACS180-
04...
in3
dm3
1-phase
Un = 208 ... 240 V
890
15
SU202M-C8
R0
02A4-1
116 Technical data
Summary of Contents for ACS180-04S-03A7-1
Page 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Page 2: ......
Page 4: ......
Page 12: ...12...
Page 24: ...24...
Page 84: ...84...
Page 96: ...96...
Page 146: ...146...
Page 148: ...Frame R0 148 Dimension drawings...
Page 149: ...Frame R1 Dimension drawings 149...
Page 151: ...Frame R3 Dimension drawings 151...
Page 152: ...Frame R4 152 Dimension drawings...
Page 160: ...160...
Page 180: ...Declarations of conformity 180 The Safe torque off function...
Page 181: ...The Safe torque off function 181...
Page 182: ...182 The Safe torque off function...
Page 183: ...The Safe torque off function 183...
Page 184: ...184...
Page 187: ...Installation 1 2 N m M4x16 2x 3 3 3 2 2 2 2 Accessories 187...
Page 189: ...Installation 3 3 2 2 2 3 2 2 N m M4x16 4x 1 Accessories 189...