Current multiplier with different switching frequencies
Type
ACS180-04...
12 kHz
8 kHz
4 kHz
2 kHz
0.4
0.6
1
1
-03A3-4
0.4
0.6
1
1
-04A0-4
0.4
0.6
1
1
-05A6-4
0.4
0.6
1
1
-07A2-4
0.4
0.6
1
1
-09A4-4
0.4
0.6
1
1
-12A6-4
0.4
0.6
1
1
-17A0-4
0.5
0.7
1
1
-25A0-4
0.6
0.7
1
1
-033A-4
0.5
0.7
1
1
-038A-4
0.5
0.7
1
1
-045A-4
0.5
0.7
1
1
-050A-4
Fuses
The tables list the fuses for protection against short-circuits in the input power
cable or drive. The operating time depends on the supply network impedance, and
the cross-sectional area and length of the supply cable.
Do not use fuses that have a higher current rating than specified in the table. You
can use fuses from other manufacturers, if they meet the ratings, and if the melting
curve of the fuse does not exceed the melting curve of the fuse mentioned in the
table.
■
IEC fuses
Either fuse type can be used if it operates rapidly enough.
gG fuses
Make sure that the operating time of the fuse is less than 0.5 seconds. Obey the
local regulations.
Technical data 109
Summary of Contents for ACS180-04S-03A7-1
Page 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Page 2: ......
Page 4: ......
Page 12: ...12...
Page 24: ...24...
Page 84: ...84...
Page 96: ...96...
Page 146: ...146...
Page 148: ...Frame R0 148 Dimension drawings...
Page 149: ...Frame R1 Dimension drawings 149...
Page 151: ...Frame R3 Dimension drawings 151...
Page 152: ...Frame R4 152 Dimension drawings...
Page 160: ...160...
Page 180: ...Declarations of conformity 180 The Safe torque off function...
Page 181: ...The Safe torque off function 181...
Page 182: ...182 The Safe torque off function...
Page 183: ...The Safe torque off function 183...
Page 184: ...184...
Page 187: ...Installation 1 2 N m M4x16 2x 3 3 3 2 2 2 2 Accessories 187...
Page 189: ...Installation 3 3 2 2 2 3 2 2 N m M4x16 4x 1 Accessories 189...