Action
Test the operation of the STO function when the motor is stopped.
•
Give a stop command for the drive (if running) and wait until the motor shaft is
at a standstill.
Make sure that the drive operates as follows:
•
Open the STO circuit. The drive generates an indication if one is defined for the
'stopped' state in parameter 31.22 (see the firmware manual).
•
Give a start command to verify that the STO function blocks the drive's operation.
The motor should not start.
•
Close the STO circuit.
•
Reset any active faults. Restart the drive and check that the motor runs normally.
Test the operation of the STO function when the motor is running.
•
Start the drive and make sure the motor is running.
•
Open the STO circuit. The motor should stop. The drive generates an indication
if one is defined for the 'running' state in parameter 31.22 (see the firmware
manual).
•
Reset any active faults and try to start the drive.
•
Make sure that the motor stays at a standstill and the drive operates as described
above in testing the operation when the motor is stopped.
•
Close the STO circuit.
•
Reset any active faults. Restart the drive and check that the motor runs normally.
Test the operation of the failure detection of the drive. The motor can be stopped
or running.
•
Open the 1st input channel of the STO circuit. If the motor was running, it should
coast to a stop. The drive generates an FA81 fault indication (see the firmware
manual).
•
Give a start command to verify that the STO function blocks the drive's operation.
The motor should not start.
•
Open the STO circuit (both channels).
•
Give a reset command.
•
Close the STO circuit (both channels).
•
Reset any active faults. Restart the drive and check that the motor runs normally.
•
Open the 2nd input channel of the STO circuit. If the motor was running, it should
coast to a stop. The drive generates an FA82 fault indication (see the firmware
manual).
•
Give a start command to verify that the STO function blocks the drive's operation.
The motor should not start.
•
Open the STO circuit (both channels).
•
Give a reset command.
•
Close the STO circuit (both channels).
•
Reset any active faults. Restart the drive and check that the motor runs normally.
Document and sign the validation test report which verifies that the safety function
is safe and accepted for operation.
The Safe torque off function 171
Summary of Contents for ACS180-04S-03A7-1
Page 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Page 2: ......
Page 4: ......
Page 12: ...12...
Page 24: ...24...
Page 84: ...84...
Page 96: ...96...
Page 146: ...146...
Page 148: ...Frame R0 148 Dimension drawings...
Page 149: ...Frame R1 Dimension drawings 149...
Page 151: ...Frame R3 Dimension drawings 151...
Page 152: ...Frame R4 152 Dimension drawings...
Page 160: ...160...
Page 180: ...Declarations of conformity 180 The Safe torque off function...
Page 181: ...The Safe torque off function 181...
Page 182: ...182 The Safe torque off function...
Page 183: ...The Safe torque off function 183...
Page 184: ...184...
Page 187: ...Installation 1 2 N m M4x16 2x 3 3 3 2 2 2 2 Accessories 187...
Page 189: ...Installation 3 3 2 2 2 3 2 2 N m M4x16 4x 1 Accessories 189...