Identifying the grounding system of the electrical power network
WARNING!
Only a qualified electrical professional may do the work instructed in this
section. Depending on the installation site, the work may even be categorized
as live working. Continue only if you are an electrical professional certified
for the work. Obey the local regulations. If you ignore them, injury or death
can occur.
To identify the grounding system, examine the supply transformer connection.
See the applicable electrical diagrams of the building. If that is not possible,
measure these voltages at the distribution board, and use the table to define the
grounding system type.
1.
input voltage line to line (U
L-L
)
2.
input voltage line 1 to ground (U
L1-G
)
3.
input voltage line 2 to ground (U
L2-G
)
4. input voltage line 3 to ground (U
L3-G
).
The table below shows the line-to-ground voltages in relation to the line-to-line
voltage for each grounding system.
Electrical power system type
UL3-G
UL2-G
UL1-G
UL-L
TN-S system (symmetrically grounded)
0.58·X
0.58·X
0.58·X
X
Corner-grounded delta system (nonsym-
metrical)
0
1.0·X
1.0·X
X
Midpoint-grounded delta system (non-
symmetrical)
0.5·X
0.5·X
0.866·X
X
IT systems (ungrounded or high-resist-
ance-grounded [>30 ohms]) nonsymmet-
rical
Varying level
versus time
Varying level
versus time
Varying level
versus time
X
TT system (the protective earth connec-
tion for the consumer is provided by a
local earth electrode, and there is anoth-
er independently installed at the gener-
ator)
Varying level
versus time
Varying level
versus time
Varying level
versus time
X
Electrical installation 67
Summary of Contents for ACS180-04S-03A7-1
Page 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Page 2: ......
Page 4: ......
Page 12: ...12...
Page 24: ...24...
Page 84: ...84...
Page 96: ...96...
Page 146: ...146...
Page 148: ...Frame R0 148 Dimension drawings...
Page 149: ...Frame R1 Dimension drawings 149...
Page 151: ...Frame R3 Dimension drawings 151...
Page 152: ...Frame R4 152 Dimension drawings...
Page 160: ...160...
Page 180: ...Declarations of conformity 180 The Safe torque off function...
Page 181: ...The Safe torque off function 181...
Page 182: ...182 The Safe torque off function...
Page 183: ...The Safe torque off function 183...
Page 184: ...184...
Page 187: ...Installation 1 2 N m M4x16 2x 3 3 3 2 2 2 2 Accessories 187...
Page 189: ...Installation 3 3 2 2 2 3 2 2 N m M4x16 4x 1 Accessories 189...