Chapter 3 – Electrical Installation
3-2
ACS/ACC/ACP 604/607 Frequency Converters
Input Cable Protection
Normal slow fuses can be used to protect the input cable in case of a
short circuit. (They do not protect the input bridge of ACx 600 in case of
a short circuit.) Slow fuses must be dimensioned according to local
safety regulations, appropriate mains voltage and the rated current of
the ACx 600 (see
Appendix A).
Cabling Instructions
Power Cables
The mains and motor cables must be dimensioned according to local
regulations:
1.
The cable must be able to carry the ACx 600 load current.
2.
The cable terminals of ACx 600 warm up to 60
°
C (140
°
F) during
operation. The cable must be rated for at least 60
°
C (140
°
F)
maximum operating temperature.
3
The cable must fulfil the requirements of the short-circuit protection
used.
4.
The inductance and impedance of the cable must be rated
according to permissible touch voltage appearing under fault
conditions (so that the fault point voltage will not rise too high when
an earth fault occurs).
The voltage rating of the mains cables should be 1 kV for 690 VAC
rated equipment. For the North American market, 600 VAC rated cable
is accepted for 600 VAC rated equipment. Voltage rating for the motor
cables should be minimum 1 kV as a general rule.
Symmetrical shielded motor cable must be used (figure below).
Four-conductor system is allowed for mains cabling, but shielded
symmetrical cable is recommended. To operate as a protective
conductor, the shield conductivity must be at least 50 % of the
conductivity of the phase lead.
Compared to a four-conductor system, the use of symmetrical shielded
cable reduces electromagnetic emission of the whole drive system as
well as motor bearing currents and wear.
The motor cable and its PE pigtail (twisted screen) should be kept as
short as possible in order to reduce electromagnetic emission as well
as capacitive current.
Summary of Contents for ACS 600 MultiDrive
Page 2: ......
Page 4: ......
Page 14: ...Safety Instructions xii ACx ACS ACC ACP ACS ACC ACP 604 607 Frequency Converters...
Page 17: ...6 3 DUGZDUH 0DQXDO Y Appendix B ACx 607 Dimensional Drawings...
Page 18: ...YL 6 3 DUGZDUH 0DQXDO...
Page 22: ...Chapter 1 Introduction 1 4 ACS ACC ACP 604 607 Frequency Converters...
Page 40: ...Chapter 3 Electrical Installation 3 16 ACS ACC ACP 604 607 Frequency Converters...
Page 44: ...Chapter 5 Maintenance 5 2 ACS ACC ACP 604 607 Frequency Converters...
Page 76: ...Appendix B ACx 607 Dimensional Drawings B 2 ACS ACC ACP 607 Frequency Converters...
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......