Chapter 3 – Electrical Installation
ACS/ACC/ACP 604/607 Frequency Converters
3-9
Transformer Settings
16. ACx 604/607 units (except frame R7 units) include a transformer
(T41) which supplies power to the cooling fan at base of the
converter unit. The transformer is set to 415 V, 500 V or 690 V at
the factory. Adjust the setting if it does not correspond to the
supply voltage. To access the transformer remove the front cover
of the converter unit with the ABB logo. After adjusting the voltage
put the plate back into its place.
17. Cabinets with the line contactor option include an internal auxiliary
voltage transformer. Its input voltage is set to 415 V, 500 V or
690 V at the factory. Adjust the setting if it does not correspond to
the supply voltage. The transformer is located in the upper right
part of the cabinet, and is visible when the cabinet door is opened.
) )
7
9
9
9
9
9
9
9
Summary of Contents for ACS 600 MultiDrive
Page 2: ......
Page 4: ......
Page 14: ...Safety Instructions xii ACx ACS ACC ACP ACS ACC ACP 604 607 Frequency Converters...
Page 17: ...6 3 DUGZDUH 0DQXDO Y Appendix B ACx 607 Dimensional Drawings...
Page 18: ...YL 6 3 DUGZDUH 0DQXDO...
Page 22: ...Chapter 1 Introduction 1 4 ACS ACC ACP 604 607 Frequency Converters...
Page 40: ...Chapter 3 Electrical Installation 3 16 ACS ACC ACP 604 607 Frequency Converters...
Page 44: ...Chapter 5 Maintenance 5 2 ACS ACC ACP 604 607 Frequency Converters...
Page 76: ...Appendix B ACx 607 Dimensional Drawings B 2 ACS ACC ACP 607 Frequency Converters...
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......