Table 1-2 ACS 300 frequency converter types for 50 Hz and
60 Hz supplies. Mains supply 380 to 480 V.
1)
Allowed for one minute every ten minutes at 50
°
C ambient.
2)
The impedance of mains supply affects the input current.
3)
The single underline (_) in the type designation stands for “0” or
“1”.
Type
designation
3)
Frame
Rated
input
current
2)
3-phase
I
1
[A]
Output current
Maximum
permissible rated
motor power
P
N
[kW]
Weight
[kg]
Rated
current
I
N
[A]
Short-term
overload
current
I
OVER
[A]
1)
ACS 3_1-1P6-3
R1
3.0
2.5
3.8
0.75
4.6
ACS 3_1-2P1-3
R1
3.9
3.2
4.8
1.1
4.6
ACS 3_1-2P7-3
R1
5.0
4.1
6.2
1.5
4.6
ACS 3_1-4P1-3
R1
7.5
6.2
9.3
2.2
4.6
ACS 3_1-4P9-3
R1
9.1
7.5
11.0
3.0
4.6
ACS 3_1-6P6-3
R1
12.1
10.0
15.0
4.0
4.6
ACS 3_1-8P7-3
R2
10.6
13.2
19.8
5.5
13.0
ACS 3_1-012-3
R2
14.4
18.0
27.0
7.5
13.0
ACS 3_1-016-3
R2
21.0
24.0
27.0
11.0
13.0